Huawei NetCol5000-A050 Quick Manual page 26

In-row air cooled smart cooling
Hide thumbs Also See for NetCol5000-A050:

Advertisement

12
Power-On
Power-On
12.1
Users are classified into admin and operator. The preset password is 000001 for both types of
users.
After powering on, the smart cooling product is in shutdown mode.
After powering on, the compressor starts preheating, and the system generates an alarm
indicating that the compressor is preheating (for 12 hours). Do not start the smart cooling
product before the preheating ends. Choose Running > Device Details > Compressor to query
the remaining preheating time.
The smart diagnosis function is available only when the outdoor unit is configured with a
temperature control intelligent monitoring board.
1. Turn on the indoor fan circuit breaker.
2. Turn on the upstream power input switch of the smart cooling product.
3. Turn on the QF1 and QF2. (You do not need to turn on the standby switch QF2 when there is
only one power supply.)
4. After the first power-on, the Quick Settings screen is displayed. On the screen, set the
language, date format, date, time, time zone, temperature control intelligent monitoring
board (open the electric control box of the outdoor unit and check whether there is a
temperature control intelligent monitoring board on the box cover. If yes, select Yes for Temp
control intelligent monitoring board under Quick Settings), smart diagnosis function (that
is, the function of detecting insufficient refrigerant and the function of energy saving control
by linkage between the indoor and outdoor units), altitude, and other parameters. If this is not
the first power-on, the home screen is displayed.
12.2
Temperature and Humidity Settings
1. Set Temperature and humidity control type, Control point temperature setpoint, and
Control point humidity setpoint as required on site. Path: Settings > System Settings >
Common Settings or Settings > System Settings > T/H Sensor.
2. If a T/H sensor outside the cabinet is installed, enable it. Path: Settings > System Settings >
Common Settings or Settings > System Settings > T/H Sensor.
12.3
(Optional) Teamwork Settings
Item (CAN network)
Team
No.
work
System
grou
address
p No.
1
1
1
2
1
2
3
1
3
...
...
...
7
1
7
8
1
8
Enable
Teamw
teamwor
ork
Networking
k CAN
functio
mode
resistor
n
Yes
Enable
No
Enable
No
Enable
...
...
No
Enable
Yes
Enable
Number
of
systems
in this
group
CAN network
8
CAN network
/
CAN network
/
CAN network
...
CAN network
/
CAN network
/
26
Number of
Rotatio
running
n
systems in
function
this group
6 (2 standby) Enable
/
/
/
/
...
...
/
/
/
/
Requir
ement
control
Enable
/
/
...
/
/