Bif-Con (Option) - Mitsubishi Electric AE630-SW Instruction Manual

Low-voltage air circuit breakers type ae, cc-link interface unit bif-md
Hide thumbs Also See for AE630-SW:
Table of Contents

Advertisement

2.2 BIF-CON (Option)

The general specifications of BIF-CON are shown in table 2.3.
Table 2.3 General
specifications of BIF-CON
Item
Type name
Power supply
Number of channel
Digital input
Isolation
Signal level
Number of channel
Digital output
Isolation
Contact capacity
External dimensions
Operating ambient temperature
Storage ambient temperature
Operating/Storage
ambient humidity
Operating/Storage ambience
Operating altitude
Installation
■1): SHT (AC380-500V) cannot be used.
BIF-CON
Supplied from BIF-CC
3 channels (INPUT1, INPUT2, INPUT3 general use)
Photo coupler isolation
12VDC, 30mA
1)
3 channels (*SHT
/CC/MD exclusive use)
Relay isolation
8A at 250V AC・DC (resistive load)
100(H) x 90(W) x 65(D)
-5 to +40℃ (However, the average of temperature per 24hours must not exceed +35℃)
-20 to +60℃ (However, the average of temperature per 24hours must not exceed +35℃)
max. 85%RH (no condensation) at the max. +40℃ in the clean air conditions.
Do not use and store in atmospheres with sulfide gas, ammonia gas, etc.
(H
S≤ 0.01ppm, SO
≤ 0.1ppm, NH
2
2
max. 2000m (6600ft.)
35mm IEC rail/Bracket
E-7
Specifications
1)
≤ 0.25ppm)
3