Mitsubishi Electric AE630-SW Instruction Manual page 20

Low-voltage air circuit breakers type ae, cc-link interface unit bif-md
Hide thumbs Also See for AE630-SW:
Table of Contents

Advertisement

Table 5.1: Communication items (3/3)
Communication items
■Items for setting (*For details, see
Date and time
year/month/day/hour/minute/second
Demand time
load current
leakage current
power (active/reactive/apparent)
Alarm holding method
EPAL
Iep
Tep
■Items for resetting
Trip and alarm status
Trip and alarm history
All max./min. measuring values
Energy values
All items
■Items for input/output contacts
Inputs
digital input (*3 channels)
Outputs
for SHT drive
for CC drive
for MD drive
■1): For details about these accessories, please see
Required
option
"5.3 Setting items (detail)"
).
-
-
E1 and ZCT
VT
-
E1 and ZCT
-
BIF-CON
BIF-CON and SHT
BIF-CON and CC
BIF-CON and MD
"AE-SW CATALOG
E-20
1)
Monitoring and setting of date and time are available.
Set the demand time used for demand measuring values.
Set the alarm holding method.
When a setting of alarm holding method is "auto reset",
the active alarm status will return to normal state automatically
if load current falls below the pickup level. On the other hand,
when a setting of alarm holding method is "self-holding",
the alarm status will remain until it is reset by reset order even
if load current falls below the pickup level.
However, PAL1 P.U., PAL2 P.U., OVER and TAL are always
returned to normal state automatically whether "auto reset"
or "self-holding".
Sets the EPAL setting values.
Reset the active trip and alarm status.
Reset the trip and alarm history.
In this case, the active trip and alarm status are also reset.
Reset all max./min. measuring values.
However, the energy values are not reset.
Reset energy values (Wh and varh values).
All items that can be reset (all items described above) are reset
These information can be monitored even if internal
transmission error has occurred.
By using BIF-CON, it is able to drive the SHT/CC/MD via
CC-Link network.
In case that the internal transmission error has occurred, these
orders are not available.
"AE-SW INSTRUCTION MANUAL"
" or