●(D) STATION NO. Switch
The BIF-CC supports the station number range from 1 through 64.
The station number is set in binary form shown as below sample.
The setting of switches is effective when power supply is turned ON.
After changing the switch while power supply is on, push RESET switch (see also
Sample setting:
Do not change the knobs with mechanical pencil.
It may cause malfunction by carbon dust.
●(E) B RATE Switch
This switch is used for baud rate setting.
Number Baud rate
0
156kbps
Factory setting
1
625kbps
2
2.5Mbps
3
5Mbps
4
10Mbps
5 to 9
Unusable
If the switch is set in these position, the "L ERR." LED lights up.
■1): If the switch is changed during operation, it should be pushed RESET switch after changing
the switch settings (see also
●(F) Connector for AE-SW internal transmission
This connector is used for internal transmission with AE-SW.
Wiring connection is shown as below.
■Note: Only one BIF-CC can be connected to AE-SW.
Internal transmission cable
(*attached to BIF-CC)
ON: 20, 8, 1
Station number: 20 + 8 + 1 = 29
Notes
"(B) RESET switch"
).
Connect to either
upside (labeled
downside (labeled
Keep distance more than 100mm
from the power distribution circuit.
Hot plugging is not
permitted
Fig 3.6: Wiring Connection
E-10
"(B) RESET switch"
STATION NO.
×10
×1
8
4
2
1
8
4
2
1
knob
I/F-1
) or
I/F-2
)
).
ON OFF
ON