Mitsubishi Electric MELSEC Q Series User Manual page 132

Hide thumbs Also See for MELSEC Q Series:
Table of Contents

Advertisement

5 UTILITY PACKAGE (GX Configurator-TC)
5 - 21
Downloaded from
ManualsNet.com
[Explanation of items]
(1) Items
Setting item
Current value : Monitors the I/O signal states and present buffer memory values.
Setting value : Enter or select values to be written into the buffer memory for test
(2) Command buttons
Current value display
Make text file
Start monitor / Stop monitor
Execute test
Close
(3) Example of using "Execute test"
The following explains the case of writing data to CH1 Set value (SV) setting.
(a) Click and choose the set value field of CH1 Set value setting (SV).
(b) After entering a value, press the Enter key.
Nothing is written to the Q64TC at this point.
(c) Click on the field, of which setting value has been changed in step (b).
(When multiple items have been changed in operation (b), select the setting
(value) fields where setting values were changed, while holding down the
Ctrl key. Multiple fields can also be selected by dragging the mouse over
them.)
(d) Click Execute test to execute the write operation.
Upon completion of writing, the written value appears in the current value
field.
search engine
: Displays I/O signals and buffer memory names.
operation.
Displays the current value of the item selected.
(This is used to check the text that cannot be
displayed in the current value field. However, in
this utility package, all items can be displayed in
the display fields).
Creates a file containing the screen data in text
file format.
Selects whether or not to monitor the current
values.
Performs a test on the selected items. To select
more than one item, select them while holding
down the Ctrl key.
Closes the screen that is currently open and
returns to the previous screen.