Installing Water Pipes
The water pipes are connected using thread connectors. The threaded joints must be sealed
with sealing tape or thread adhesive.
Clean the external water pipes before connecting them to the water inlet and outlet pipes.
Connect the water inlet and outlet pipes of the FusionCol8000-E using thread connectors.
When connecting the water pipes, do not exert excessive force to prevent damage to the
pipes. (When connecting the pipes, use two pipe wrenches or chain pliers.)
At low temperatures, take thermal insulation measures to prevent water pipes from
freezing.
Water pipes must be wrapped with thermal insulation foam (including the buried pipes).
Designed water trap height
It is recommended that height
B be a smaller value.
Pipe Position and Relative Position Dimensions
FDC Scenario
(1) Water refill pipe of the water tank
1.
Remove sheet metal for drainpipes.
2.
Install the condensate water pan
drainpipe, evaporator condensate
water pan drainpipe, and water tank
drainpipe.
3.
Install the floor drain pipe (in the
building scenario).
Unit: mm
(1) Water tank drainpipe
(2) Evaporator condensate drainpipe
(3) Condensate water pan drainpipe