Download Print this page

Mitsubishi Electric 800 Series Instruction Manual page 62

Hide thumbs Also See for 800 Series:

Advertisement

Appendix 2
(Standard to comply with: UL 508C, CSA C22.2 No.274-13)
 General precaution
CAUTION - Risk of Electric Shock -
The bus capacitor discharge time is 10 minutes. Before starting wiring or inspection, switch power off, wait for more than 10 minutes, and check for residual
voltage between terminal P/+ and N/- with a meter etc., to avoid a hazard of electrical shock.
ATTENTION - Risque de choc électrique -
La durée de décharge du condensateur de bus est de 10 minutes. Avant de commencer le câblage ou l'inspection, mettez l'appareil hors tension et attendez plus
de 10 minutes.
 Installation
The below types of inverter have been approved as products for use in enclosure and approval tests were conducted under the following conditions.
Design the enclosure so that the surrounding air temperature, humidity and ambience of the inverter will satisfy the specifications. (Refer to
 Branch circuit protection
For installation in the United States, Class T, Class J, Class CC, or Class L fuse, UL 489 Molded Case Circuit Breaker (MCCB), or Type E combination motor
controller must be provided, in accordance with the National Electrical Code and any applicable local codes.
For installation in Canada, Class T, Class J, Class CC, or Class L fuse, UL 489 Molded Case Circuit Breaker (MCCB), or Type E combination motor controller
must be provided, in accordance with the Canadian Electrical Code and any applicable local codes.
For the FR-F820 series, Class T, Class J, or Class CC fuse, UL 489 Molded Case Circuit Breaker (MCCB), or Type E combination motor controller must be
provided.
FR-F820-[]
Rated fuse voltage (V)
Without power factor improving reactor
Fuse allowable rating
(A)
With power factor improving reactor
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)

Maximum current rating (A)
Type E combination
motor controller

Maximum SCCR (kA)
FR-F820-[]
Rated fuse voltage (V)
Without power factor improving reactor
Fuse allowable rating
(A)
With power factor improving reactor
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)

Maximum current rating (A)
Type E combination
motor controller
Maximum SCCR (kA)
FR-F840-[]
Rated fuse voltage (V)
Without power factor improving reactor
Fuse allowable rating
(A)
With power factor improving reactor
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)

Maximum current rating (A)
Type E combination
motor controller

Maximum SCCR (kA)
FR-F840-[]
Rated fuse voltage (V)
Without power factor improving reactor
Fuse allowable rating
(A)
With power factor improving reactor
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)

Maximum current rating (A)
Type E combination
motor controller
Maximum SCCR (kA)

Maximum allowable rating by the US National Electrical Code. Exact size must be chosen for each installation.

Select an appropriate molded case circuit breaker with a rating that is suitable for the size of the cable.

For UL/cUL certification, use the following product.
Model
MMP-T32

Suitable for use in a circuit capable of delivering not more than 50 or 25 kA rms symmetrical amperes, 480Y/277 volts maximum when protected by the Type E
combination motor controllers indicated in the above table.

Type E combination motor controller is combination of Manual motor starter, Short-circuit Display Unit "UT-TU" and Power Side Terminal Cover Kit "UT-CV3".
 Wiring to the power supply and the motor
Refer to the National Electrical Code (Article 310) regarding the allowable current of the cable. Select the cable size for 125% of the rated current according to the
National Electrical Code (Article 430).
For wiring the input (R/L1, S/L2, T/L3) and output (U, V, W) terminals of the inverter, use the UL listed copper, stranded wires (rated at 75
terminals. Crimp the terminals with the crimping tool recommended by the terminal manufacturer.
Instructions for UL and cUL
00046
00077
(0.75K)
(1.5K)
240 V or more
15
20
15
20
15
15
8
13
50
50

00930
01250
(22K)
(30K)
240 V or more
225
300
200
250
225
300
00023
00038
(0.75K)
(1.5K)
500 V or more
6
10
6
10
15
15
4
6.3
50
50

00930
01160
(45K)
(55K)
500 V or more
200
250
175
200
225
250
Manufacturer
Mitsubishi Electric Corp.
00105
00167
00250
00340
00490
(2.2K)
(3.7K)
(5.5K)
(7.5K)
(11K)
30
40
60
80
150
20
30
50
70
125
25
40
60
80
110
18
25
32
50
25
25
01540
01870
02330
03160
03800
(37K)
(45K)
(55K)
(75K)
(90K)
350
400
500
300
350
400
500
600
350
450
500
700
900
00052
00083
00126
00170
00250
(2.2K)
(3.7K)
(5.5K)
(7.5K)
(11K)
15
20
30
40
70
10
15
25
35
60
15
20
30
40
60
8
13
18
25
32
50
50
50
25
25
01800
02160
02600
03250
03610
(75K)
(90K)
(110K)
(132K)
(160K)
250
300
350
400
500
450
450
500
Rated voltage, VAC
480Y/277
page
3.)
00630
00770
(15K)
(18.5K)
175
200
150
200
150
190
04750
(110K)
700
1000
00310
00380
00470
00620
00770
(15K)
(18.5K)
(22K)
(30K)
(37K)
80
90
110
150
175
70
90
100
125
150
70
90
100
150
175
04320
04810
05470
06100
06830
(185K)
(220K)
(250K)
(280K)
(315K)
600
700
800
900
1000
) and round crimping
°C
Appendix
21

Hide quick links:

Advertisement

loading