Setting
Pr.
Name
Pre-charge upper
0 to 100%,
763
detection level
9999
764
Pre-charge time limit
0 to 3600s, 9999 9999
Second pre-charge
765
0, 1
fault selection
Second pre-charge
0 to 100%,
766
ending level
9999
Second pre-charge
0 to 3600s,
767
ending time
9999
Second pre-charge
0 to 100%,
768
upper detection level
9999
Second pre-charge
0 to 3600s,
769
time limit
9999
1 to 3, 5 to 14,
Operation panel
774
17, 18, 20,
monitor selection 1
23 to 25, 34, 38,
Operation panel
40 to 45,
775
monitor selection 2
50 to 57, 61, 62,
64, 67 to 69,
Operation panel
81 to 96,
776
monitor selection 3
98,100, 9999
4 mA input check
0 to 590Hz,
777
operation frequency
9999
778
4 mA input check filter
0 to 10s
Operation frequency
0 to 590Hz,
779
during communication
9999
error
Acceleration time in
0 to 3600s,
791
low-speed range
9999
Deceleration time in
0 to 3600s,
792
low-speed range
9999
Pulse increment setting
0.1, 1, 10, 100,
799
for output power
1000kWh
800
Control method selection 9, 20, 109, 110 20
820
Speed control P gain 1 0 to 1000%
Speed control integral
821
0 to 20s
time 1
822
Speed setting filter 1
0 to 5s, 9999
Torque control P gain 1
824
(current loop
0 to 500%
proportional gain)
Torque control integral
825
time 1 (current loop
0 to 500ms
integral time)
827
Torque detection filter 1 0 to 0.1s
828
Parameter for manufacturer setting. Do not set.
Speed control P gain 2 0 to 1000%,
830
9999
Speed control integral
831
0 to 20s, 9999 9999
time 2
832
Speed setting filter 2
0 to 5s, 9999
834
Torque control P gain 2 0 to 500%, 9999 9999
Torque control integral
0 to 500ms,
835
time 2
9999
837
Torque detection filter 2 0 to 0.1s, 9999 9999
Analog input offset
849
0 to 200%
adjustment
Terminal 4 function
858
0, 4, 9999
assignment
0 to 500A,
9999
Torque current/Rated
859
PM motor current
0 to 3600A,
9999
0 to 500A,
Second motor torque
9999
860
current/Rated PM
0 to 3600A,
motor current
9999
864
Torque detection
0 to 400%
Torque monitoring
866
0 to 400%
reference
867
AM output filter
0 to 5s
Terminal 1 function
868
0, 4, 9999
assignment
869
Current output filter
0 to 5s

Speed detection
870
0 to 5Hz
hysteresis
Input phase loss
872
0, 1
protection selection
874
OLT level setting
0 to 400%
Regeneration
882
avoidance operation
0 to 2
selection
Regeneration
883
avoidance operation
300 to 800V
level
Regeneration avoidance
884
at deceleration detection
0 to 5
sensitivity
Regeneration avoidance
0 to 590Hz,
885
compensation frequency
9999
limit value
Regeneration
886
0 to 200%
avoidance voltage gain
888
Free parameter 1
0 to 9999
889
Free parameter 2
0 to 9999
Cumulative power monitor
891
0 to 4, 9999
digit shifted times
16
Parameter list
Initial
Pr.
range
value
892
Load factor
9999
Energy saving monitor
893
reference (motor
capacity)
0
Control selection during
9999
894
commercial power-
supply operation
9999
Power saving rate
895
reference value
9999
896
Power unit cost
Power saving monitor
897
9999
average time
Power saving cumulative
898
9999
monitor clear
Operation time rate
899
(estimated value)
9999
C0
FM/CA terminal
(900)
calibration

9999
C1
AM terminal calibration ―
(901)

9999
C2
Terminal 2 frequency
(902)
setting bias frequency

0s
C3
Terminal 2 frequency
(902)
setting bias

9999
125
Terminal 2 frequency
(903)
setting gain frequency

9999
C4
Terminal 2 frequency
(903)
setting gain

9999
C5
Terminal 4 frequency
(904)
setting bias frequency

1kWh
C6
Terminal 4 frequency
(904)
setting bias

126
Terminal 4 frequency
25%
(905)
setting gain frequency

0.333s
C7
Terminal 4 frequency
(905)
setting gain

9999
C12
Terminal 1 bias
(917)
frequency (speed)

50%
C13
Terminal 1 bias (speed) 0 to 300%
(917)

C14
Terminal 1 gain
40ms
(918)
frequency (speed)

C15
0s
Terminal 1 gain (speed) 0 to 300%
(918)

C16
Terminal 1 bias command
(919)
(torque/magnetic flux)

9999
C17
Terminal 1 bias (torque/
(919)
magnetic flux)

C18
Terminal 1 gain command
9999
(920)
(torque/magnetic flux)

C19
Terminal 1 gain (torque/
(920)
magnetic flux)

9999
C8
Current output bias
(930)
signal

100%
C9
Current output bias
(930)
current

0
C10
Current output gain
(931)
signal


9999
C11
Current output gain
(931)

current

C38

Terminal 4 bias command
(932)
9999
(torque/magnetic flux)


C39
Terminal 4 bias (torque/
150%
(932)
magnetic flux)

150%
C40
Terminal 4 gain command
(933)
0.01s
(torque/magnetic flux)

0
C41
Terminal 4 gain (torque/
(933)
magnetic flux)
0.02s

C42
0Hz
PID display bias
(934)
coefficient

0
C43
PID display bias analog
(934)
120/110%

value

C44
PID display gain
0
(935)
coefficient

C45
PID display gain analog
DC380/
(935)
value

DC760V

Input voltage mode
977
selection
0
Parameter copy alarm
989
release
990
PU buzzer control
6Hz
991
PU contrast adjustment 0 to 63
100%
Operation panel setting
9999
992
dial push monitor
9999
selection
9999
Setting
Initial
Name
range
value
30 to 150%
100%
Inverter
0.1 to 55kW

LD/SLD
rated
0 to 3600kW

capacity
0 to 3
0
0, 1, 9999
9999
0 to 500, 9999 9999
0, 1 to 1000h,
9999
9999
0, 1, 10, 9999 9999
0 to 100%,
9999
9999

0 to 590Hz
0Hz
0 to 300%
0%
0 to 590Hz
60/50Hz
0 to 300%
100%
0 to 590Hz
0Hz
0 to 300%
20%
0 to 590Hz
60/50Hz
0 to 300%
100%
0 to 590Hz
0Hz
0%
0 to 590Hz
60/50Hz
100%
0 to 400%
0%
0 to 300%
0%
0 to 400%
150%
0 to 300%
100%
0 to 100%
0%
0 to 100%
0%
0 to 100%
100%
0 to 100%
100%
0 to 400%
0%
0 to 300%
20%
0 to 400%
150%
0 to 300%
100%
0 to 500.00,
9999
9999
0 to 300%
20%
0 to 500.00,
9999
9999
0 to 300%
100%
0, 1
0
10
10


100
100


0, 1
1
58
0 to 3, 5 to 14,
17, 18, 20,
23 to 25, 34, 38,
40 to 45,
0
50 to 57, 61, 62,
64, 67 to 69,
81 to 96, 98,100
Pr.
Name
997
Fault initiation
0 to 255, 9999 9999
0, 12, 14, 112,
PM parameter
114, 8009,
998

initialization
8109, 9009,
9109

Automatic parameter
1, 2,10 to 13,
999

setting
20, 21, 9999
1000
Direct setting selection 0 to 2
Lq tuning target current
50 to 150%,
1002
adjustment coefficient
9999
1006
Clock (year)
2000 to 2099
101 to 131,
201 to 229,
301 to 331,
401 to 430,
501 to 531,
601 to 630,
1007
Clock (month, day)
701 to 731,
801 to 831,
901 to 930,
1001 to 1031,
1101 to 1130,
1201 to 1231
0 to 59,
100 to 159,
200 to 259,
300 to 359,
400 to 459,

500 to 559,
600 to 659,
700 to 759,
800 to 859,
900 to 959,
1000 to 1059,
1100 to 1159,
1008
Clock (hour, minute)
1200 to 1259,
1300 to 1359,
1400 to 1459,

1500 to 1559,
1600 to 1659,
1700 to 1759,
1800 to 1859,
1900 to 1959,
2000 to 2059,
2100 to 2159,
2200 to 2259,
2300 to 2359
Running speed after

1013
emergency drive retry
0 to 590Hz
reset
Integral stop selection
1015
0 to 2, 10 to 12 0
at limited frequency
PTC thermistor
1016
0 to 60s
protection detection time
Monitor with sign
1018
0, 1, 9999
selection
1020
Trace operation selection 0 to 4
1021
Trace mode selection
0 to 2
1022
Sampling cycle
0 to 9
Number of analog
1023
1 to 8
channels
1024
Sampling auto start
0, 1
1025
Trigger mode selection 0 to 4
Number of sampling
1026
0 to 100%
before trigger
Analog source selection
1027
(1ch)
Analog source selection
1028
(2ch)
1 to 3, 5 to 14,
Analog source selection
1029
17, 18, 20, 23,
(3ch)
24, 34,
Analog source selection
40 to 42,
1030
(4ch)
52 to 54, 61,
62, 64, 67, 68,
Analog source selection
1031
81 to 96, 98,
(5ch)
201 to 213,
Analog source selection
230 to 232,
1032
(6ch)
237, 238
Analog source selection
1033
(7ch)
Analog source selection
1034
(8ch)
1035
Analog trigger channel 1 to 8
Analog trigger
1036
0, 1
operation selection
1037
Analog trigger level
600 to 1400
Digital source selection
1038
(1ch)
Digital source selection
1039
(2ch)
Digital source selection
1040
(3ch)
Digital source selection
1041
(4ch)
1 to 255
Digital source selection
1042
(5ch)
Digital source selection
1043
(6ch)
Digital source selection
1044
(7ch)
Digital source selection
1045
(8ch)
1046
Digital trigger channel
1 to 8
Setting
Initial
range
value
0
9999
0
9999
2000
101
0
60/50Hz

0s
9999
0
0
2
4
0
0
90%
201
202
203
204
205
206
207
208
1
0
1000
1
2
3
4
5
6
7
8
1