• Use the inverter under the conditions of overvoltage category II (usable regardless of the earth (ground) condition of the power supply), overvoltage
category III (usable with the earthed-neutral system power supply, 400 V class only) and pollution degree 2 or lower specified in IEC 60664. An insulating
transformer needs to be installed in the input side of the FR-F820 series inverters.
• To use the inverter of FR-F820-01250(30K) or higher and FR-F840-00770(37K) or higher (IP00) under the conditions of pollution degree 2, install it in the
enclosure of IP 2X or higher.
• To use the inverter under the conditions of pollution degree 3, install it in the enclosure of IP54 or higher.
• To use the inverter of FR-F820-00930(22K) or lower and FR-F840-00620(30K) or lower (IP20) outside of an enclosure in the environment of pollution
degree 2, fix a fan cover with fan cover fixing screws enclosed.
• On the input and output of the inverter, use cables of the type and size set forth in EN 60204-1 or IEC 60364-5-52.
• The operating capacity of the relay outputs (terminal symbols A1, B1, C1, A2, B2, C2) should be 30VDC, 0.3A. (Relay output has basic isolation from the
inverter internal circuit.)
• Control circuit terminals on
page 5
• Environment (For the detail, refer to
During Operation
LD rating: -10 to +50°C
Surrounding air temperature
SLD rating: -10 to +40°C
Ambient humidity
95% RH or less
Maximum altitude
2500 m

For the installation at an altitude above 1000 m, consider a 3% reduction in the rated current per 500 m increase in altitude.
 Branch circuit protection
Class T, Class J, Class CC, or Class L fuse, or UL 489 Molded Case Circuit Breaker (MCCB) must be provided.
For the FR-F820 series, Class T, Class J, or Class CC fuse, or UL 489 Molded Case Circuit Breaker (MCCB) must be provided. (Use a product which
conforms to the EN or IEC Standard.)
FR-F820-[]
Rated fuse voltage (V)
Without power factor improving reactor 15
Fuse allowable
rating (A)
With power factor improving reactor
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)

FR-F820-[]
Rated fuse voltage (V)
Without power factor improving reactor 225
Fuse allowable
rating (A)
With power factor improving reactor
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)

FR-F840-[]
Rated fuse voltage (V)
Without power factor improving reactor 6
Fuse allowable
rating (A)
With power factor improving reactor
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)

FR-F840-[]
Rated fuse voltage (V)
Without power factor improving reactor 200
Fuse allowable
rating (A)
With power factor improving reactor
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)


Maximum allowable rating by US National Electrical Code. Exact size must be chosen for each installation.
 Short circuit ratings
• 200 V class
Suitable For Use in A Circuit Capable of Delivering Not More Than 100 kA rms Symmetrical Amperes, 240 V Maximum.
• 400 V class
Suitable For Use in A Circuit Capable of Delivering Not More Than 100 kA rms Symmetrical Amperes, 500 V Maximum.
Fan cover
fixing screw
Fan cover
Fan
FR-F820-00105(2.2K) to 00250(5.5K)
FR-F840-00083(3.7K), 00126(5.5K)
are safely isolated from the main circuit.
page
3.)
In Storage
-20 to +65°C
95% RH or less
2500 m

00046
00077
00105
(0.75K)
(1.5K)
(2.2K)
240 V or more
20
30
15
20
20
15
15
25
00930
01250
01540
(22K)
(30K)
(37K)
240 V or more
300
350
200
250
300
225
300
350
00023
00038
00052
(0.75K)
(1.5K)
(2.2K)
500 V or more
10
15
6
10
10
15
15
15
00930
01160
01800
(45K)
(55K)
(75K)
500 V or more
250
175
200
250
225
250
450
Fan cover
fixing screw
Fan cover
Fan
FR-F820-00340(7.5K) to 00930(22K)
FR-F840-00170(7.5K) to 00620(30K)
During Transportation
-20 to +65°C
95% RH or less
10000 m
00167
00250
00340
00490
00630
(3.7K)
(5.5K)
(7.5K)
(11K)
(15K)
40
60
80
150
175
30
50
70
125
150
40
60
80
110
150
01870
02330
03160
03800
04750
(45K)
(55K)
(75K)
(90K)
(110K)
400
500
350
400
500
600
700
450
500
700
900
1000
00083
00126
00170
00250
00310
(3.7K)
(5.5K)
(7.5K)
(11K)
(15K)
20
30
40
70
80
15
25
35
60
70
20
30
40
60
70
02160
02600
03250
03610
04320
(90K)
(110K)
(132K)
(160K)
(185K)
300
350
400
500
600
450
500
00770
(18.5K)
200
200
190
00380
00470
00620
00770
(18.5K)
(22K)
(30K)
(37K)
90
110
150
175
90
100
125
150
90
100
150
175
04810
05470
06100
06830
(220K)
(250K)
(280K)
(315K)
700
800
900
1000
Appendix
19