Lift The Fixed Circuit Breaker Or The Moving Part Of A Withdrawable Circuit-Breaker - ABB SACE Emax 2 Installation, Operation And Maintenance Instructions

Table of Contents

Advertisement

Lift the fixed circuit breaker
or the moving part of a
withdrawable circuit-breaker
13 | © 2021 ABB | 1SDH002083A1002 - ECN000119014 - Rev. A
Continued from the previous page
Standards
Current
UL 489B
3200A
2500A
2000A
1600A
UL 489B
UL 489F
2500A
2000A
1600A
(*)
Terminals supplied not assembled
NOTE:
• the indicated weights refer to fixed circuit-breakers with rear terminals without accessories.
• the weights of the fixed part refer to the version with vertical rear terminals and, if present, with
jumpers.
WARNING! Improper lifting can result in death, serious injury to persons and damage
to the equipment. Never lift a circuit-breaker and / or a fixed part above other people.
IMPORTANT: The trained personnel in charge of handling and lifting must use
appropriate safety equipment.
To lift the circuit-breaker:
1.
Raise the circuit-breaker from the base of the packaging with the aid of the lifting plates supplied with
the circuit-breaker. See Figure 14 and Figure 15.
Figure 14
To raise the fixed part of the circuit-breaker
1.
Lift the fixed part from the base of the package using the purpose-made lifting points of the fixed part.
See Figure 16.
IMPORTANT: keep the lifting plates and manual until the disconnector is dismantled.
Fixed 4p
Configuration
Kg
Lbs
4ps
122 (*)
270 (*)
2ps
130 (*)
286 (*)
122 (*)
270 (*)
4ps
109
240
109
240
130 (*)
286 (*)
2ps
105
231
105
231
Figure 15
ABB | SACE Emax 2
Withdrawable
Fixed part 4p
4p
Kg
Lbs
Kg
98 (*)
105 (*)
98 (*)
84
80
176
84
105 (*)
78
78
Figure 16
Management operations | 2 - Unpacking and handling
Lbs
216 (*)
232 (*)
216 (*)
185
185
232 (*)
172
172

Advertisement