Table of Contents

Advertisement

15.2 OPERATION OF VACUUM CIRCUIT-BREAKER

B
A
Mechanical position indicators:
A:
Green push-button closes the switch
B:
Red push-button opens the switch
C:
Mechanical position indication, circuit-breaker open
D:
Mechanical position indication, earthing switch closed
Vacuum circuit-breaker:
Charging springs: Turn the operating handle clockwise
to charge the closing and the opening spring.
Close: Push the green button (A)
Open: Push the red button (B)
The isolator in the V-module can only be opened after the
circuit-breaker is opened. Then the circuit-breaker can be
closed for testing purposes.
C
D
Switch disconnector:
Close: Turn the operating handle clockwise.
Open: Turn the operating handle anti-clockwise.
Earthing switch:
Close: Turn the operating handle clockwise.
Open: Turn the operating handle anti-clockwise.
27

Advertisement

Table of Contents
loading

This manual is also suitable for:

Safeplus

Table of Contents