Mitsubishi Electric LOSSNAY LGH-F300RX5-E Handbook page 42

Hide thumbs Also See for LOSSNAY LGH-F300RX5-E:
Table of Contents

Advertisement

No.
Error
3
Interlock operation
with external device
does not occur.
Note: When two remote controllers are used, the combination of the PZ-60DR-E and PZ-41SLB-E cannot be used.
System checklist when using the M-NET ( Table 1-2-2 )
No.
Error
1
Lossnay does not in-
terlock with City Multi
indoor unit. ( Lossnay
cannot be operated by
the ventilation button on
the ME remote control-
ler, MA remote controller
or MELANS. )
2
Cannot operate using
MELANS or the Lossnay
remote controller.
3 A Lossnay unit should
operate independently
by MELANS or the
Lossnay remote control-
ler, but it interlocks with
different City Multi units.
Cause
 The interlock mode is set to " ON Interlocked "
or " OFF Interlocked " with the remote controller
( PZ-60DR-E ) .
 The interlock mode is set to " 2 " ( ON Interlocked )
or " 3 " ( OFF Interlocked ) with PZ-41SLB-E.
 When PZ-60DR-E and PZ-41SLB-E are not
used, the delay setting switch ( SW5-1 ) on the
Lossnay circuit board is set to ON. ( During the
delay operation, LED1 ( green ) on the Lossnay
circuit board will be lit. )
 When PZ-60DR-E and PZ-41SLB-E are not
used, the interlock mode setting switches ( SW5-
7, SW5-8 ) on the Lossnay circuit board are set
to " ON Interlocked " or " OFF Interlocked " .
 When multiple Lossnay units are used, the
external control input signal is connected to a
unit set to " Sub " .
 Remote/local switching ( CN32 ) is used.
 Lossnay is not set for interlock operation,
or is set for interlock operation at the wrong
address.
 The length of the M-NET transmission cable wir-
ing from the outdoor unit or the system's overall
wiring length is longer than specified. ( Longer
than 219 yd. (200 m) from the outdoor unit,
longer than 547 yd. (500 m) between ends. )
 PZ-41SLB-E is connected to Lossnay.
 The address that has been set for the
group in MELANS and the address for the
Lossnay are different.
 The length of the M-NET transmission ca-
ble wiring from the power supply unit or the
system's overall wiring length is longer than
specified. ( Longer than 219 yd. (200 m)
from the power supply unit, longer than 547
yd. (500 m) between ends. )
 PZ-41SLB-E is connected to Lossnay.
 It has been set for interlock operation with
the City Multi units.
Cause
─ 42 ─
Action
 Check the Interlock mode setting
with the remote controller ( PZ-
60DR-E ) . ( Refer to page 24 )
 Check the Interlock mode setting
with the remote controller ( PZ-
41SLB-E ) . ( Refer to page 24 )
 Check the setting of the delay
setting switch ( SW5-1 ) on the
Lossnay circuit board. ( Refer to
page 30 )
 Check the setting of the interlock
mode setting switch ( SW5-7,
SW5-8 ) on the Lossnay circuit
board. ( Refer to page 30 )
 Connect the external control
input signal to the Lossnay unit
set to " Main. "
 When interlocked with external
devices, remote/local switching
( CN32 ) cannot be used.
Action
 Check the Lossnay address, and
set for an address corresponding
to interlock operation.
 Check the length of the transmis-
sion cable wiring.
( See the technical manual for
details about the regulations. )
 Change the remote controller to
PZ-60DR-E or PZ-52SF-E. (PZ-
41SLB-E cannot be used with the
M-NET.)
 Check the registered address in
MELANS.
 Check the length of the transmis-
sion cable wiring.
( See the technical manual for
details about the regulations. )
 Change the remote controller to
PZ-60DR-E or PZ-52SF-E. (PZ-
41SLB-E cannot be used with the
M-NET.)
 Cancel the interlock operation
setting.