Signal cables from external devices ( Table 1-1-3 )
Check the following checkpoints when connecting with level signal/pulse signal output devices, and Mr. Slim units.
No.
Do the transmission cables meet regulations? ( Type, diameter )
1
2
Is the signal cable wired at least 2 in. (5 cm) away from the power
supply cable?
3
Are multiple transmission or signal cables wired to the same power
cable duct?
4
Are multiple signal cables wired with multi core cables?
5
Are the signal cables securely connected to the terminals?
6
Are the signal cables connected to the specified terminal blocks?
Mr. Slim control signal: TM2 1, 2
Charged signal: TM2 1, 2
Uncharged a-contact signal: TM2 1, 3
7
Is the wiring length of the signal cable within the regulations?
Mr. Slim control signal: Total extension within 547 yd. (500 m)
Charged signal: Within limitation of the external device
Uncharged a-contact signal: Total extension within 547 yd. (500 m)
8
Do the external signals meet specifications?
Level signal: Charged 12 V DC/ 24 V DC, uncharged a-contact
Pulse signal: Charged 12 V DC/ 24 V DC, uncharged a-contact
( A pulse width of 200 ms or greater is required )
9
Are the type of input signal and the setting of the pulse input
matched?
Pulse signal: ON setting
Other than pulse signal : OFF setting
10
In a system with multiple Lossnay units, are the signal cables con-
nected to the specified Lossnay unit?
Basic system ( PZ-60DR-E, PZ-41SLB-E ) :
Lossnay unit for which the Main/Sub selection switch ( SW1 ) is set to
" Main "
M-Net control:
Lossnay unit that is set to the address with the smallest number
within the group
11
When PZ-60DR-E is not used, are the function selection switches
( SW2, SW5 ) on the Lossnay circuit board set correctly?
12
When PZ-60DR-E is used, is the function selection set correctly?
Checkpoint
─ 39 ─
Action
Use specified cables.
Wire the signal cable at least 2 in.
(5 cm) away from the power sup-
ply cable.
Wire the transmission cables
away from the signal cables.
Use suitable cables to wire the
signal cables so that they are
separated from one another.
Connect them securely.
Connect them to the specified
terminal blocks.
Wire the cables within the regula-
tions.
Input a signal that suits the speci-
fications.
<When using PZ-60DR-E>
Check the pulse input setting from
the function selection. ( Refer to
page 34 )
<When not using PZ-60DR-E>
Check the setting of the pulse
input switch ( SW2-2 ) on the
Lossnay circuit board. ( Refer to
page 30 )
Connect the signal cables to the
specified Lossnay unit.
Set the switches correctly to cor-
respond with the application.
( Refer to page 30 and 31 )
Set it correctly to correspond with
the application.
( Refer to page 32 to 34 )