Mitsubishi Electric LOSSNAY LGH-F300RX5-E Handbook page 17

Hide thumbs Also See for LOSSNAY LGH-F300RX5-E:
Table of Contents

Advertisement

( 3 ) Fan control
1 Fan speed control for each system
The control indicated below can be performed according to the system that is paired.
Up to two of the Lossnay remote controllers PZ-60DR-E, PZ-41SLB-E, and PZ-52SF-E can
be used in the same group, but they cannot be used together with a different remote control-
ler. When using two remote controllers, be sure to use the same model of remote controller.
Caution
PZ-41SLB-E cannot be used in M-NET control. When controlling Lossnay in M-NET control,
use PZ-60DR-E or PZ-52SF-E.
When using PZ-60DR-E and mixing the LGH-F300 to F600 types together with the LGH-
F1200 type in a group, set the LGH-F300 to F600 types as "Main".
System Configuration
Stand-alone/
multiple Lossnay
and Lossnay
remote controller:
PZ-60DR-E
Stand-alone/
multiple Lossnay
and Lossnay
remote controller:
PZ-41SLB-E
System interlocked
with Mr. Slim
Level signal/pulse
signal
System interlocked
with the output
device
Stand-alone/
multiple Lossnay
and Lossnay
remote controller:
PZ-60DR-E
Stand-alone/multi-
ple Lossnay and
Lossnay remote
controller:
PZ-52SF-E
M-NET
Lossnay central
control system
M-NET
System interlocked
with City Multi
indoor units
Remote controllers
System controllers
Lossnay remote
The remote controller "Fan Speed Adjustment" button permits
High ( Extra High ) /Low fan speed selection, and the "Extra Low fan
controller
PZ-60DR-E
SPEED" button permits an extra low fan speed selection.
( The LGH-F1200 type does not provide Extra Low fan speed opera-
tion. )
Lossnay remote
The remote controller "Fan Speed Adjustment" button permits High
( Extra High ) /Low fan speed selection.
controller
( Extra Low fan speed selection is not available from the remote con-
PZ-41SLB-E
troller. )
A-control remote
The A-control remote controller "Ventilation" button permits High
( Extra High ) /Low fan speed selection.
controller
K-control remote
( High ( Extra High ) /Low fan speed selection is not available from the
K-control remote controller. )
controller
( Remote control-
( Extra Low fan speed selection is not available from the A-control
and K-control remote controllers. )
ler connection
prohibited with
Lossnay )
Fixed to High ( Extra High ) fan speed.
None
Lossnay remote
The remote controller "Fan Speed Adjustment" button permits High
( Extra High ) /Low fan speed selection, and the "Extra Low fan speed"
controller
PZ-60DR-E
button permits an Extra Low fan speed selection.
( The LGH-F1200 type does not provide Extra Low fan speed opera-
tion. )
Lossnay remote
The remote controller "Fan Speed Adjustment button" permits High
( Extra High ) /Low fan speed selection.
controller
( Extra Low fan speed selection is not available from the Lossnay
PZ-52SF-E
remote controller. )
M-NET controller The system remote controller, or centralized control remote control-
ler "Fan Speed" button or "Ventilation setting" button permits High
( Extra High ) /Low fan speed selection.
( The ON/OFF remote controller and the schedule timer do not permit
fan speed selection. )
( Extra Low fan speed selection is not available from the system
remote controller or the centralized control remote controller. )
The remote controller "Ventilation" button permits High ( Extra High ) /
ME remote con-
troller
Low fan speed selection.
( Extra Low fan speed selection is not available from the ME remote
PAR-F27MEA,
controller and MA remote controller. )
MA remote con-
troller
PAR-20/21MAA
Fan speed
─ 17 ─

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents