s-AIRME-G02/G07
INSTALLATION, USE AND MAINTENANCE MANUAL
Italian is the original language.
The other languages versions are translation of the original.
To ensure safe and correct use, carefully read this manual and make sure to understand all the contained indications
and information.
Installation, use and maintenance manual
English
English
1

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Electric s-AIRME-G02

  • Page 1 Air-handling units s-AIRME-G02/G07 INSTALLATION, USE AND MAINTENANCE MANUAL English English Italian is the original language. The other languages versions are translation of the original. To ensure safe and correct use, carefully read this manual and make sure to understand all the contained indications and information.
  • Page 2 Before carrying out any operation on the machine, you must carefully read this manual and make sure you understand all the instructions and information given. Keep this manual in a known and easily accessible place to refer to as necessary during the entire life-span of the machine. This Manual has been prepared by MEHITS S.p.A.: Reproduction, even partial, of this booklet is prohibited.
  • Page 3: Table Of Contents

    Installation of the standard machiine ........................50 4.2.2 Machine positioning ............................... 53 4.2.3 Joining the sections ............................... 54 2.2.4 CONNECTION OF THE COOLING CIRCUIT BETWEEN S-AIRME-G02/G07 AND MR. SLIM UNIT ......56 HYDRAULIC CONNECTIONS ............................. 58 4.3.1 Hydraulic connection to water coils ........................58 4.3.2 Installation technical notes ............................
  • Page 4 MACHINE START-UP ..............................91 8 ..METHOD OF USE ........................92 PROVISIONS AND WARNINGS FOR USE ........................ 92 DESCRIPTION OF CONTROLS ..........................92 EMERGENCY STOP ..............................92 PROLONGED SHUTDOWNS OF THE MACHINE ...................... 92 START-UP AFTER EXTENDED MACHINE INACTIVITY ................... 93 9 ..
  • Page 5: General Provisions

    1 GENERAL PROVISIONS 1.1 General information and safety 1.1.1 Scope of the manual This manual, which is an integral part of the machine (1), was prepared by the Manufacturer to provide the necessary information to all those who are authorised to interact with it during its life span: Buyers, System Designers, Carriers, Handling Operators, Installers, Expert Operators, Specialist Technicians and Users.
  • Page 6: Symbols

    2 SYMBOLS DANGER: Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. WARNING: Warning indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. ATTENTION: Attention indicates a potentially hazardous situation which, if not avoided, could cause minor or moderate damage.
  • Page 7: Glossary And Terminology

    3 GLOSSARY AND TERMINOLOGY There are some recurring terms in the manual which are described below in more detail. Manufacturer: this is the company that has designed and built the machine in line with current laws, implementing all the good construction rules, and paying attention to the health and safety of people interacting with the machine.
  • Page 8: Attached Documentation

    3.1 Attached documentation The following documents are delivered with the unit: • Installation, use and maintenance manual (multilingual): this manual accompanies the unit and contains the main installation, use and maintenance information. • Installation, use and maintenance manual (extended): in electronic format and available on the manufacturer's website, it offers detailed information on the installation, use and maintenance steps set out in the multilingual manual supplied with the machine.
  • Page 9 permitted dimensions for transport on the vehicle. Apply any necessary signs. The operator must have read and understood the information on use of the machine, and have suitable skills and experience for carrying out the work in hand. Put the machine only to the uses foreseen by the manufacturer. Improper use of the machine may pose risks to the health and safety of the persons and cause financial losses.
  • Page 10: Proper And Improper Use

    3.1.1.1 Proper and improper use Use the unit only for the intended purposes for which it was designed. Any other use relieves Mehits of all liability arising from improper use of the unit. Air-handling units are designed for civil and industrial air handling. In case of corrosive and/or explosive operating environments, during the design stage it is essential to make the machine suitable for handling particular flows.
  • Page 11 Prevention of residual electrical risks • The unit contains live parts that could cause serious injury or death. Only personnel trained in electrical hazards should work on electrical and electronic components, such as electrical panels, motors, wiring. Personnel must wear the appropriate personal protective equipment for the activities at all times, including, for example, gloves, dielectric shoes and face shield, and use dielectric tools;...
  • Page 12 • Do not store inflammable liquids near the unit; • Solder or braze only empty pipes after removing all traces of lubricant oil; do not use flames or other heat sources in the vicinity of pipes containing cooling fluid; • Do not use naked flames near the unit;...
  • Page 13: List Of Machine Internal Symbols

    3.1.3 List of machine internal symbols The unit is fitted with the necessary safety signs; here are some examples: 3.1.3.1 Precautions against residual risks GENERAL This chapter contains information on the correct handling of units containing flammable fluid R32, with reference to European regulations and directives.
  • Page 14 Some of the properties of R32 are listed below: ASHRAE/ ISO817 Name PED Group ASHRAE Safety Classification ODP (Ozone Depletion Potential) (R11 = 1) GWP (Global Warming Potential) AR5 (AR4) (CO2 = 1) 677 (675) Saturated Liquid Temperature(1) @ 1 atm -51.65 Practical Limit (kg/m3) 0061...
  • Page 15 INSTALLATION • The units can be installed both inside machinery rooms and outdoors. For indoor installations such as semi-basements, basements or machinery rooms, these must comply with EN 378-3:2021 - par. 5 requirements (gas detection, ventilation, alarm system, etc.). • The refrigerant is heavier than air and can stagnate, e.g.
  • Page 16: Minimum Installation Area For Units With R32

    MINIMUM INSTALLATION AREA FOR UNITS WITH R32 The unit must be selected according to the minimum square footage given in the table below, referring to the smallest room served by the unit at the installation site. The unit itself cannot be intended as a safety feature for the indoor environment. The responsibility for proper installation and safety of the environments served by the unit rests entirely with the installer.
  • Page 17 This damper keeps the unit in communication with the outside environment, ensuring the evacuation of any refrigerant leakage. For further information refer to the dedicated chapter 4.6. MAINTENANCE The following precautions must be taken before working on the refrigerant circuit: •...
  • Page 18 Persons working on the unit shall have competence in the safety aspects of handling flammable refrigerants, supported by evidence of appropriate training. This will include the following requirements: • Knowledge of legislation, regulations and standards relating to flammable refrigerants; • Detailed knowledge of and skill in handling flammable refrigerants, personal protective equipment, refrigerant leakage prevention, handling of cylinders, charging, leak detection, recovery and disposal.
  • Page 19 Description of the LEDs The sensor board has a status LED and two relays. Open the casing housing the sensor to check the status of the LED. The two relays detect the presence of gas (alarm) and the presence of faults in the sensor (fault). The status of the analogue output, relays and signalling LEDs are shown in the following tables: Start-up and normal operation: Service instrument LED...
  • Page 20 Commissioning Commissioning must only be carried out by authorised Mitsubishi Electric personnel. Remove the sensor head cap when commissioning the unit. Perform a documented functional test without gas. After the functional test has been completed, record the maintenance carried out in the controller of the Rooftop unit. The next maintenance should be performed within 12 months.
  • Page 21 Zero calibration The potentiometer adjustment in the figure is performed without applying any gas. • Connect the multimeter to the test pin (shown in red in the figure) and GND earth (pay attention to the connection diagram on the board). Measure the voltage with respect to earth (GND).
  • Page 22: Procedure For Requesting Support

    Identification plate: the machine type can be found on the label attached directly to the machine. The label provides the reference data and all the essential information required to ensure safe operation DESIGNATION IDENTIFICATION PLATE s-AIRME-G02 AR C 3000 s-AIRME Series -G02-...
  • Page 23: Storage Temperature

    Check the operating range of the Mr. Slim condensing units in their documentation. 3.4.2 Operating limits INFORMATION: The operating range of the s-AIRME-G02/G07 units is as follows (values referring to the temperature of the fresh air at the inlet of the s-AIRME-G02/G07): • Minimum temperature: -20 °C •...
  • Page 24 AR FUNCTION version I s-AIRME s-AIRME s-AIRME s-AIRME s-AIRME MODEL AIRME AIRME 7500 10000 12500 15000 20000 3000 5000 [m3/h] 3000 5000 7500 10000 12500 15000 20000 Air flow [m3/h] 1500 - 2500- 4000- 6000- 9000- 10000- 14000- Air flow range 3000 5000 7500...
  • Page 25 MF FUNCTION version C(100% fresh air) s-AIRME s-AIRME s-AIRME s-AIRME MODEL AIRME AIRME AIRME 10000 12500 15000 20000 3000 5000 7500 [m3/h] 3000 5000 7500 10000 12500 15000 20000 Air flow [m3/h] 1000 - 2000- 4000- 6000- 9000- 10000- 14000- Air flow range 3000 5000...
  • Page 26 MF FUNCTION version B (100% fresh air) s-AIRME s-AIRME s-AIRME s-AIRME AIRM AIRME AIRME 10000 12500 15000 20000 MODEL 5000 7500 3000 3000 5000 7500 10000 12500 15000 20000 Air flow 2000 - 3500- 4600- 6000- 9000- 10000- 14000- Air flow range 3000 5000 7500...
  • Page 27 HR-P FUNCTION version I s-AIRME s-AIRME s-AIRME s-AIRME s-AIRME s-AIRME MODEL 3000 5000 7500 10000 12500 15000 [m3/h] 3000 5000 7500 10000 12500 15000 Air flow [m3/h] 2300 - 3950- 5900- 7850- 9100- 11750- Air flow range 3000 5000 7500 10000 12500 15000...
  • Page 28 HR-P FUNCTION version B s-AIRME s-AIRME s-AIRME s-AIRME s-AIRME s-AIRME MODEL 3000 5000 7500 10000 12500 15000 [m3/h] 3000 5000 7500 10000 12500 15000 Air flow [m3/h] 2800 - 4550- 6500- 9100- 11350- 13600- Air flow range 3000 5000 7500 10000 12500 15000...
  • Page 29: Characteristics Of Machines With R32 Refrigerant

    3.4.4 Characteristics of machines with R32 refrigerant AR FUNCTION version C s-AIRME s-AIRME s-AIRME s-AIRME MODEL AIRME AIRME AIRME 10000 12500 15000 20000 3000 5000 7500 [m3/h] 3000 5000 7500 10000 12500 15000 20000 Air flow [m3/h] 1000 - 2000- 4000- 6000- 9000-...
  • Page 30 AR FUNCTION version B s-AIRME s-AIRME s-AIRME s-AIRME s-AIRME s-AIRME s-AIRME MODEL 3000 5000 7500 10000 12500 15000 20000 [m3/h] 3000 5000 7500 10000 12500 15000 20000 Air flow [m3/h] 2000 - 3500- 4600- 6000- 9000- 10000- 14000- Air flow range 3000 5000 7500...
  • Page 31 FUNZIONE MF versione I (100% fresh air) s-AIRME s-AIRME s-AIRME s-AIRME s-AIRME s-AIRME s-AIRME MODEL 3000 5000 7500 10000 12500 15000 20000 [m3/h 3000 5000 7500 10000 12500 15000 20000 Air flow [m3/h 1500 - 2500- 4000- 6000- 9000- 10000- 14000- Air flow range 3000...
  • Page 32 HR-P FUNCTION version C s-AIRME s-AIRME s-AIRME s-AIRME s-AIRME s-AIRME MODEL 3000 5000 7500 10000 12500 15000 [m3/h] 3000 5000 7500 10000 12500 15000 Air flow [m3/h] 2000 - 3250- 4250- 6200- 7850- 8450- Air flow range 3000 5000 7500 10000 12500 15000...
  • Page 33 HR-P FUNCTION version I s-AIRME s-AIRME s-AIRME s-AIRME s-AIRME s-AIRME MODEL 3000 5000 7500 10000 12500 15000 [m3/h] 3000 5000 7500 10000 12500 15000 Air flow [m3/h] 2300 - 3950- 5900- 7850- 9100- 11750- Air flow range 3000 5000 7500 10000 12500 15000...
  • Page 34 FUNZIONE HR-P versione B s-AIRME s-AIRME s-AIRME s-AIRME s-AIRME s-AIRME MODEL 3000 5000 7500 10000 12500 15000 [m3/h] 3000 5000 7500 10000 12500 15000 Air flow [m3/h] 2800 - 4550- 6500- 9100- 11350- 13600- Air flow range 3000 5000 7500 10000 12500 15000...
  • Page 35: General Description

    The units in the s-AIRME-G02/G07 series control the external air intake and are characterised by exceptional energy efficiency and a high level of configurability.
  • Page 36: Mf Function - Mixing And Free Cooling

    MF function – Mixing and Free cooling 3.5.3 When compared with the baseline configuration, this unit has 2 opposite motor-driven dampers managed by the machine controller, for air recirculation only, mixed, or free cooling operation. With this function it is possible to mix the recirculation air from the environment (yellow arrow) with a certain amount of fresh air (red arrow), either a fixed value set using the controller, or a variable value modulated by the CO2 air quality probe (optional).
  • Page 37: Unit Configuration

    3.5.5 Unit configuration For each size, s-AIRME-G02/G07 is available in 3 different versions for 3 different power levels: • Version C: version suitable for the handling of neutral air. The direct expansion coil and the respective combination with Mr.Slim units are not sized to achieve complete conditioning of the handled air, but only for recirculation and/or air exchange.
  • Page 38 Combination of s-AIRME-G02/G07 units and Mr. Slim outdoor units The units in the s-AIRME-G02/G07 series are combined with the Mr. Slim direct expansion outdoor units to guarantee the required performance in both heating and cooling mode. The Mr. Slim outdoor units are combined with the three versions of...
  • Page 39 HR-P FUNCTION • Combinations for s-AIRME-G02/G07 version C s-AIRME- s-AIRME- s-AIRME- s-AIRME- s-AIRME- s-AIRME- Outdoor G02/G07 G02/G07 G02/G07 G02/G07 G02/G07 G02/G07 Units 3000 5000 7500 10000 12500 15000 Size P125 Size P140 Size P200 Size P250 • Combinations for s-AIRME-G02/G07 version I...
  • Page 40: Description Of The Main Components

    All versions, from full recirculation to the unit with plate heat recovery, are encompassed in a single one-piece structure, making the s-AIRME-G02/G07 units in which handling and installation on site are greatly simplified. The standard machine configuration includes inspections (removable panels) and refrigerant and water connections on the right.
  • Page 41: Electrical Panel

    3.6.5 Air filter The s-AIRME-G02/G07 series of machines are supplied with air filters with COARSE 55% efficiency according to ISO 16890 (G4 according to EN 779), 98 mm thick. The filters are placed on steel guides, which can be accessed easily for routine maintenance and replacement. Optionally, it is possible to choose between pre-filters with different degrees of efficiency.
  • Page 42: Packaging Of Standard Units

    Packaging of standard units In their standard packaging, units are supplied with air inlet and air outlet protections. They are also supplied with lifting and handling brackets. Two possible packaging solutions are available on request: • Shrink wrapping: the standard packaging is further protected with shrink wrapping and reinforced corners. •...
  • Page 43 Dimensions and weight of standard units HR-P function LENGTH WIDTH HEIGHT VERS. WEIGHT C VERS. WEIGHT I VERS. WEIGHT B SIZE [mm] [mm] [mm] [kg] [kg] [kg] s-AIRME 3000 2950 1385 1675 s-AIRME 5000 2950 1785 1675 s-AIRME 7500 3200 1885 2200 1250...
  • Page 44: Transport, Storage And Installation

    4 TRANSPORT, STORAGE AND INSTALLATION 4.1 Transport and moving 4.1.1 General transport, handling and storage information During transport and when not installed immediately upon receipt, the machine should be kept in its packaging in a closed and dry location, away from direct sunlight. Temperature and humidity limits for transportation and storage Temperature and humidity limits Minimum temperature...
  • Page 45 The lifting gear and accessories must be in good condition and must be prepared, installed, maintained, monitored, checked, tested, operated and used in accordance with the manufacturer's instructions, the rules of good practice and the domestic laws and regulations that apply. The lifting equipment and/or ropes and/or other lifting accessories to be fitted between the lifting device and the load (chains, slings, hooks, sling bars) are not provided by the manufacturer.
  • Page 46: Receipt And Inspection

    INFORMATION: The data on the name plates of s-AIRME-G02/G07 units only refer to such units. For information regarding Mr. Slim condensing units, refer to the relative documentation.
  • Page 47: Handling

    4.1.5 Handling Before handling the unit, carefully read the instructions below and the indications of the yellow label on the product and in the lifting drawing, as well as the instruction manual of the lifting equipment used. WARNING: Lift one package at a time. PROHIBITION: Do not lift sections that are joined together.
  • Page 48   1) HOLES FOR LIFTING PIPES Implement the following measures: Handle the unit at an ambient temperature above -10°C and when there is no wind. Make sure that no unit components are damaged and that they are correctly installed. Use all, and only, the lifting points indicated in the dimensional drawing and marked on the unit.
  • Page 49: Loading And Unloading From Containers

    In any case, always secure the unit on the support base. The vibration dampers may extend outside the span of the machine and, in which case, will require suitable support. In the case of installation on a raised surface, make sure that the handle of the power disconnector is easy to access and at a height of between 0.6.6 m and 1.9 m above the floor (EN60204-1).
  • Page 50: Installation

    4.2 Installation 4.2.1 Installation of the standard machiine OBLIGATION: Refer to the specific Manual. WARNING: All the installation stages must be included in the general system design. Before installing the equipment, it is mandatory to carry out the following checks: •...
  • Page 51 • The unit must be installed according to the requirements of standard EN 378-3 and the local regulations in force, in particular taking into account the category of occupation of the premises and the safety class defined by EN 378-1. Refrigerant R410A Safety class...
  • Page 52 Check the dimensions of the accessories/options in the relevant chapter. The distance between the s-AIRME-G02/G07 units and the Mr. Slim condensing units should be such that the length of the connections of the cooling circuits does not exceed 30 m.
  • Page 53: Machine Positioning

    4.2.2 Machine positioning Before placing the unit in its final position, remove the shims/slides from the base (if provided). It is advisable to place an elastic rubber seal between the base of the machine and the floor, covering the entire support surface, to prevent the transmission of noise and vibrations.
  • Page 54: Joining The Sections

    4.2.3 Joining the sections The procedure for joining the sections of a unit after lifting is as follows: Check that the order of the sections is exactly the same as shown in the dimensional drawing. Check that the side with the connectors and inspection doors of the sections is as desired. Position the sections so that all the connections and inspection doors are on the same side.
  • Page 55 Insert and tighten the screw on the plate side to Locate the hexagonal inserts near the edge of the modules. ensure correct coupling. Fix the connecting plate on the base at the dedicated Insert and secure the two screws on the first and second half of the plate.
  • Page 56: Connection Of The Cooling Circuit Between S-Airme-G02/G07 And Mr. Slim Unit

    Mr. Slim units. The DE coil of the s-AIRME-G02/G07 units is composed of a number of circuits equal to the number of Mr. Slim condensing units to be combined with the air handling unit; there is a circuit for each Mr. Slim.
  • Page 57 The panel of the s-AIRME-G02/G07 unit for the manifold outlet of the direct expansion coil has a protective plate. Attention: plastic collars are applied to prevent damage to the copper pipes entering and leaving the coil. Before brazing, remove the collars from the panel (both on the inside and on the outside).
  • Page 58: Hydraulic Connections

    4.3 Hydraulic connections OBLIGATION: The execution of the hydraulic connection must be carried out by qualified personnel. All the works, the choice of the components and the materials used must comply with the "Good Practices", according to the regulations in force in the different countries, taking into account the intended operating conditions of the system.
  • Page 59: Water Quality

    4.3.4 Water quality OBLIGATION: The values shown in the table must be guaranteed during the entire life cycle of the machine. Description Symbol Range values Hydrogen ions 7.5 - 9 Presence of calcium (Ca) and magnesium (Mg) Hardness 4 ÷ 8.5 °D Chloride ions <...
  • Page 60: Anti-Freeze Solutions

    4.4 Hydraulic connection of the condensate drain Hydraulic connection of the condensate drain To connect the condensate drain, follow the instructions below both for the s-AIRME-G02/G07 unit and for the humidification section accessory. Standard supply The condensate drain pipe is connected to the collection tank.
  • Page 61: Electrical Connections

    WARNING: No part of the drain line should be uphill. The connection pipes must be suitably supported so that they do not weigh down on the machine. 4.5 Electrical connections The electrical connections of the machine must be defined during the system design. DANGER: The electrical connections must only be designed and completed by personnel with precise technical competence or particular skills in the field of activity.
  • Page 62: Control Circuit Interlocking

    Mr. Slim condensing units. It is forbidden to connect Mr. Slim condensing units to the switchboard of the s-AIRME-G02/G07 units. 4.5.2 Control circuit interlocking It is imperative to always check the wiring diagram before completing the connections: In the electrical panel are some cables and terminals, indicated in orange, that remain powered even with the power disconnector open (circuits excluded).
  • Page 63 Signal connections The Mr. Slim condensing units must be electrically connected to the s-AIRME-G02/G07 units only by means of the cables required to send signals between the PAC-IF interface board and the Mr. Slim condensing units.
  • Page 64 Incorrect connection of the signal cables between the PAC-IF interface card and the Mr. Slim condensing units can cause irreparable damage to, and malfunctioning of the connected machines. The s-AIRME-G02/G07 unit has a cable gland, as shown in the photo, for the signals described above. WARNING: All electric work must be designed and performed by qualified personnel.
  • Page 65: Air Connections

    Do not remove the safety nets in the unit. The s-AIRME-G02/G07 units can be connected to the air ducts either directly by means of the aluminium profiles of its structure or by fixing the ducts to the dampers, if ordered.
  • Page 66 During normal operation of the unit, the rate of the air flow treated by the fans is sufficient to ensure that no hazardous mixtures can form inside the machine pursuant to the EN 378 standard as indicated in the table in chapter 3.1.3.1. Units with R32 refrigerant charge are supplied as standard with delivery and return air dampers belonging to class CL4 according to the EN1751:2014 standard, and which close when the unit is not in operation.
  • Page 67: Options

    WARNING: If there is a loss of refrigerant, call technical assistance before restarting the machine. WARNING: Avoid having the ducts putting weight on the machine or any components of the same (frames, panels, pipes, etc...). 4.7 Options OBLIGATION: All assembly, positioning and maintenance operations must be carried out with adequate means and by skilled personnel, trained and authorized for this type of manoeuvres.
  • Page 68 Optional extras on additional section For the s-AIRME range, most of the optional extras are designed as additional sections to be attached to the base unit in the order shown in the picture below. LEGEND: A: 3-way mixing chamber (only for HR-P function) B: Photocatalytic oxidation sanitation system (PCO) C: Electric/water post-heating D: Humidifier...
  • Page 69 Electric post-heating coil (additional section option) The electric post-heating coil can be used in winter to compensate for the defrost cycles of the outdoor units. In the case of defrost, one or more circuits of the direct expansion coil may temporarily produce cold air instead of the flow of hot air expected during normal operation in this season.
  • Page 70 -10°C by modulating the 3-way valve serving the coil to give the air a temperature rise of up to 5°C. Pre-heating ΔP [kPa] P [kW] Q [l/h] Size of unit S-AIRME-G02/G07 3000 5.14 28.20 S-AIRME-G02/G07 5000 8.56 1631 23.20 S-AIRME-G02/G07 7500 12.84...
  • Page 71 Install an expansion vessel with a safety valve in the hydraulic circuit. The hydraulic circuit must be sized according to the applicable laws in force. The hydraulic circuit must not obstruct the opening of the inspection doors of the s-AIRME-G02/G07 unit, and must not obstruct removal of the heat exchanger.
  • Page 72 The s-AIRME-G02/G07 units require hydraulic connections to the condensate drains and to the inlets and outlets of the pre and post-heating coils available as accessories. The inlet and outlet are marked with these labels affixed directly on the machine. INLET...
  • Page 73 In the interest of ensuring the high performance and energy efficiency of the air handling unit, there must be a differential pressure switch for each filtering section of the control system of the s-AIRME-G02/G07 units. The controller triggers an alarm when the pressure switch detects a drop in pressure that exceeds the maximum permitted value, indicating the filter concerned.
  • Page 74 The s-AIRME-G02/G07 control system can be integrated with a CO sensor. Once a threshold level has been set for the CO content in the return air, the s-AIRME-G02/G07 control system operates in the following ways: • Air flow modulation on two levels, minimum and maximum: the air flow of the fans is set to the minimum level when the CO is below the threshold level, and automatically set to the maximum level when the threshold is exceeded.
  • Page 75 The section comes with a drip tray. The delivered steam flow rate is calculated according to the size of the s-AIRME-G02/G07 unit and the power consumption of the steam generator is defined in relation to this.
  • Page 76: Disclosure Requirement (Eu) No. 1253/2014

    Length (mm) 1100 1500 5 DISCLOSURE REQUIREMENT (EU) NO. 1253/2014 s-AIRME 3000 AR/MF Δp = 500 Pa Ecodesign information requirements Manufacturer's name Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A. Model s-AIRME 3000 AR / MF Typology NRVU, UVU Nominal flow rate [m³/s]...
  • Page 77 5000 AR/MF Δp = 500 Pa Ecodesign information requirements Manufacturer's name Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A. Model s-AIRME 5000 AR / MF Typology NRVU, UVU Nominal flow rate [m³/s] 1,39 [W/(m³/s)] limit [W/(m³/s)] Face velocity [m/s]...
  • Page 78 10000 AR/MF Δp = 500 Pa Ecodesign information requirements Manufacturer's name Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A. Model s-AIRME 10000 AR / MF Typology NRVU, UVU Nominal flow rate [m³/s] 2,78 [W/(m³/s)] limit [W/(m³/s)] Face velocity [m/s]...
  • Page 79 15000 AR/MF Δp = 500 Pa Ecodesign information requirements Manufacturer's name Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A. Model s-AIRME 15000 AR / MF Typology NRVU, UVU Nominal flow rate [m³/s] 4,17 [W/(m³/s)] limit [W/(m³/s)] Face velocity [m/s]...
  • Page 80 3000 HR-P Δp = 500 Pa Ecodesign information requirements Manufacturer's name Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A. Model s-AIRME 3000 HR-P Typology NRVU, BVU Type of HRS Cross flow heat recovery Thermal efficiency of heat recovery 73,2 Nominal flow rate [m³/s]...
  • Page 81 5000 HR-P Δp = 500 Pa Ecodesign information requirements Manufacturer's name Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A. Model s-AIRME 5000 HR-P Typology NRVU, BVU Type of HRS Cross flow heat recovery Thermal efficiency of heat recovery 73,2 Nominal flow rate [m³/s]...
  • Page 82 7500 HR-P Δp = 500 Pa Ecodesign information requirements Manufacturer's name Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A. Model s-AIRME 7500 HR-P Typology NRVU, BVU Type of HRS Cross flow heat recovery Thermal efficiency of heat recovery 74,6 Nominal flow rate [m³/s]...
  • Page 83 10000 HR-P Δp = 500 Pa Ecodesign information requirements Manufacturer's name Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A. Model s-AIRME 10000 HR-P Typology NRVU, BVU Type of HRS Cross flow heat recovery Thermal efficiency of heat recovery 73,8 Nominal flow rate [m³/s]...
  • Page 84 12500 HR-P Δp = 500 Pa Ecodesign information requirements Manufacturer's name Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A. Model s-AIRME 12500 HR-P Typology NRVU, BVU Type of HRS Cross flow heat recovery Thermal efficiency of heat recovery 73,5 Nominal flow rate [m³/s]...
  • Page 85 15000 HR-P Δp = 500 Pa Ecodesign information requirements Manufacturer's name Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A. Model s-AIRME 15000 HR-P Typology NRVU, BVU Type of HRS Cross flow heat recovery Thermal efficiency of heat recovery 73,3 Nominal flow rate [m³/s]...
  • Page 86: Pre-Commissioning

    Check the filters for cleanliness. In fact, in some cases the units are only switched on in ventilation mode long before the first start-up. This causes the filters to become dirty. The Mr. Slim units and the s-AIRME-G02/G07 unit must be properly positioned according to the instructions given in the respective manuals.
  • Page 87 Below is the detail of the control board of a Mr. Slim unit with the DIP SWITCH SW8-3 in the position indicated in the aforementioned Mitsubishi Electric manual. Each Mr. Slim unit must also be "addressed". Addressing is performed by positioning the DIP SWITCHES SW1 of the control board of the Mr.
  • Page 88 Mr. Slim units. Once the vacuum is created, open the valves on the Mr. Slim units. The s-AIRME-G02/G07 unit must be connected with suitable ducts to the room where the air is to be taken out or sent. Electrically connect the Mr. Slim units and the s-AIRME-G02/G07 unit independently with reference to their manuals.
  • Page 89 : direct expansion coil The s-AIRME-G02/G07 unit is delivered with the TH2 and TH5 thermistors, which are required for correct operation of the unit, already in their probe sumps. It is forbidden to change the position the thermistors as to do so could affect correct operation and safety of the unit.
  • Page 90 After doing the above, the technician entrusted with starting the machine can proceed with the software checks and then initial start-up. INFORMATION: The PAC-IF interface cards in the switchboard of the s-AIRME-G02/G07 unit are addressed at the factory. Installation, use and maintenance manual...
  • Page 91: Start

    7 START 7.1 Calibration and fine-tuning Commissioning must be carried out by a specialist engineer, in the presence of the installer and an experienced operator. The specialist engineer will test the equipment, carrying out checks, calibrations and commissioning according to the applicable procedures falling under their responsibility.
  • Page 92: Method Of Use

    8 METHOD OF USE 8.1 Provisions and warnings for use During the daily use of the system, the presence of an operator is not required. The operator must only intervene to carry out periodic checks, in case of emergency, or during the planned start and stop operations. If these activities are carried out consistently and correctly, good long-term performance of the machine and the equipment will result.
  • Page 93: Start-Up After Extended Machine Inactivity

    IT IS advisable that the start-up after the standstill period is performed by a qualified technician. During start-up, follow the instructions in the "COMMISSIONING" section. Plan the work of the technician in advance in order to avoid any misunderstandings and to ensure that the system is ready when required.
  • Page 94 FAULT PART POSSIBLE CAUSE/SOLUTION Refer to the manual of the external condensing unit (e.g. check gas Low cooling pressure Refrigerant circuit charge, compressor delivery temperature ...) Incorrect gas/liquid pipe connection Battery Coil dirty Insufficient heat Presence of non-condensate in the direct expansion coil capacity Refer to the manual of the external condensing unit (e.g.
  • Page 95: Maintenance

    10 MAINTENANCE 10.1 Maintenance instructions WARNING: All ordinary and extraordinary maintenance activities must be carried out by specialist personnel appointed by the manufacturer or its authorised representative. Maintenance operations are fundamental to keep the refrigeration system in perfect working order, not only for purely functional reasons, but also to save energy and ensure safety.
  • Page 96 • before generating a vacuum in the cooling circuit, make sure to disconnect from the power supply all the phases of the electric motor of the compressors by removing or disconnecting the electrical protections (fuses and/or automatic switch) upstream of the cooling circuit. After charging with refrigerant, put the protections back in place with the power turned off before start-up;...
  • Page 97: Scheduled Maintenance

    10.2 Scheduled maintenance Carry out all the scheduled maintenance activities at the indicated intervals. INFORMATION: Failure to carry out regular maintenance will make the warranty null and void and relieve the manufacturer of all safety related responsibilities. Machine booklet Provide a machine booklet for keeping a record of the maintenance work carried out on the unit. In this way, it will be easier to properly plan maintenance work and any fault finding.
  • Page 98: Table Of General Maintenance Jobs

    10.3 Table of general maintenance jobs For periodic maintenance of the elements of the refrigeration circuit, as well as for checking its correct operation, refer to the manual of the condensing unit connected to the unit. FREQUENCY OPERATIONS Every days months months months...
  • Page 99: Structure Check

     Checking the anti-vibration supports.  Check tightness of fan screws and bolts.  Check that the fan turns without obstructions in the absence of voltage.  Painting the inside and outside of the air-handling unit  Check condition of the unit gaskets. ...
  • Page 100: Air Filter Maintenance/Replacement

    In the interest of ensuring the high performance and energy efficiency of the air handling unit, there must be a differential pressure switch for each filtering section of the control system of the s-AIRME-G02/G07 units that can trigger an alarm when the drop in pressure at the filter exceeds the maximum permitted value.
  • Page 101: Steam Humidifier Check

    10.8 Steam humidifier check Regular checks. • After one hour of operation In the case of both disposable cylinders and openable cylinders, check for any significant water leaks. • Every 15 days and after no more than the first 300 operating hours In the case of both disposable cylinders and openable cylinders, check operation and for any significant water leaks, and assess the general condition of the container.
  • Page 102 Checking the readings of the probes/positioning of the probes REFERENCE DESCRIPTION 1-6TH2 LIQUID TEMPERATURE PROBE (1÷6) 1-6TH5 TWO-PHASE TEMPERATURE PROBE (1÷6) 1-6TH11 COIL INPUT TEMPERATURE PROBE (1÷6) 3E1-3 PRE-HEATING ELECTRIC HEATERS (1÷3) 4E1-3 POST-HEATING ELECTRIC HEATERS (1÷3) 5BD1 HUMIDIFIER CONDUCTIVITY SENSOR 5BL1 HUMIDIFIER LEVEL SENSOR "KUE”...
  • Page 103 HR-P function probes positioning Installation, use and maintenance manual...
  • Page 104 The DIP SWITCHES of the SW1, SW2, SW3, SW6 must be set in the same way for all the PAC-IF interface cards in the switchboard of the s-AIRME-G02/G07 unit. WARNING: When the s-AIRME-G02/G07 unit is combined with a single Mr. Slim unit, dip-switch 8 of SW1 must be in the OFF position.
  • Page 105 Irrespective of the type of control used, remove the "bridge" shown in the figure: Installation, use and maintenance manual...
  • Page 106: Disposal Of The Machine

    11 DISPOSAL OF THE MACHINE When dismantling the machine, contact a service centre, distribution or branch authorised by the Manufacturer. OBLIGATION: The machine contains fluorinated greenhouse gases regulated by the Kyoto protocol. In accordance with the law, these must not be dispersed in the environment but collected and delivered to the retailer or collection centre.