Signal cables to external devices ( Table 1-1-4 )
Check the following checkpoints when outputting the operation monitor, air supply fan operation monitor, mal-
function monitor, bypass operation monitor, and operation monitor with delay function.
No.
Do the signal cables meet regulations? ( Type, diameter )
1
2
Is the signal cable wired at least 2 in. (5 cm) away from the power
supply cable?
3
Are multiple transmission or signal cables wired to the same power
cable duct?
4
Are multiple signal cables wired with multi core cables?
5
Are the signal cables securely connected to the terminals?
6
Are the signal cables connected to the specified terminal blocks?
Operation monitor, operation monitor with delay function 1: TM4 9, 0
Malfunction monitor: TM3 7, 8
Bypass operation monitor, operation monitor with delay function 2: TM3 6, 7
7
Are the output capacities of the operation monitor, malfunction moni-
tor, and bypass operation monitor within the ratings?
Output
Operation monitor
Operation monitor with delay function 1
Malfunction monitor
Bypass operation monitor
Operation monitor with delay function 2
8
When the operation monitor is used, is the setting of the output signal
correct?
9
When the operation monitor with delay function is used, is the setting
of the output signal correct?
10
When PZ-60DR-E is not used, are the function selection switches
( SW2, SW5 ) on the Lossnay circuit board set correctly?
11
When PZ-60DR-E is used, is the function selection set correctly?
Checkpoint
Maximum rating
Minimum rating
230 V AC 2 A
208 V AC 100 mA
24 V DC 2 A
5 V DC 100 mA
230 V AC 1 A
208 V AC 100 mA
24 V DC 1 A
5 V DC 100 mA
230 V AC 1 A
208 V AC 100 mA
24 V DC 1 A
5 V DC 100 mA
─ 40 ─
Action
Use specified cables.
Wire the signal cable at least 2 in.
(5 cm) away from the power sup-
ply cable.
Wire the transmission cables
away from the signal cables.
Use suitable cables to wire the
signal cables so that they are
separated from one another.
Connect them securely.
Connect them to the specified
terminal blocks.
Use them within the ratings.
<When using PZ-60DR-E>
Check the operation monitor set-
ting from the function selection.
( Refer to page 33 )
<When not using PZ-60DR-E>
Check the setting of the operation
monitor ( SW5-2 ) on the Lossnay
circuit board. ( Refer to page 30 )
Check the settings of the TM4 9,
0 output setting (SW2-8), and the
TM3 6, 7 output setting (SW5-6)
on the Lossnay circuit board.
(Refer to page 30)
Set the switches correctly to cor-
respond with the application.
( Refer to page 30 and 31 )
Set it correctly to correspond with
the application.
( Refer to page 32 to 34 )