Mitsubishi Electric LOSSNAY LGH-F300RX5-E Handbook page 29

Hide thumbs Also See for LOSSNAY LGH-F300RX5-E:
Table of Contents

Advertisement

Night Purge mode is active; no operation
1:00 A.M.
No
Outdoor
No
temperature 62.6°F (17°C)/
82.4°F (28°C) or more (within
24 hours)
Temperature monitoring
operation (5 minutes)
Indoor temperature > 71.6°F (22°C)
Indoor temperature - Outdoor temperature
> 41.0°F (5°C)
Yes
Night Purge operation
(Bypass ventilation)
6:00 A.M.
Finish Night Purge
operation (Stop)
*1: When Lossnay is interlocked with the City Multi indoor units, "Stop of Lossnay during interlocked opera-
tion with the City Multi operating in cooling mode" is another necessary condition in addition to that of
"Detection of an outdoor temperature of 62.6°F (17°C) or 82.4°F (28°C) or higher ( within 24 hours ) ".
( Night Purge operation will be performed when either of these necessary conditions has been satisfied. )
Yes
The outdoor temperature (OA) setting can be selected either 62.6°F (17°C) or
82.4°F (28°C) by using Dip-Switch (SW2-7) in the Lossnay control box.
Refer to the remote controller installation manual for more information.
*1
Yes
and
No
Yes
No
55-minute stop
Night Purge
operation
No
─ 29 ─
Yes

Hide quick links: