Huawei NetCol8000-A Series Quick Manual page 3

In-room air cooled smart cooling product
Hide thumbs Also See for NetCol8000-A Series:
Table of Contents

Advertisement

Mapping Between Saturation Temperatures and Pressure of R410A
Saturation
Gauge
temperature (º C)
(MPa)
10
0.99
11
1.02
12
1.05
13
1.09
14
1.12
15
1.16
16
1.19
17
1.23
18
1.27
2.2
Oil Trap and Inverted Trap
Unit: mm
1 inch Gas pipe
inverted trap
Saturation
temperature (º C)
19
20
21
22
23
24
25
26
27
7/8 inch Oil trap
7/8 inch Gas pipe
inverted trap
Gauge
Saturation
(MPa)
temperature (º C)
1.31
28
1.35
29
1.39
30
1.43
31
1.47
32
1.51
33
1.56
34
1.60
35
1.65
36
1 inch Oil trap
3/4 inch Liquid
pipe inverted trap
3
Gauge (MPa)
1.69
1.74
1.79
1.84
1.89
1.94
1.99
2.05
2.10
5/8 inch Liquid
pipe inverted trap