7.4
Connecting the Equipotential Bonding Cable
Equipotential bonding point
7.5
(Optional) Connecting a Differential Pressure Sensor
1. Secure the differential pressure sensor inside the cabinet using two M3 screws.
2. Connect the longer PU hose to the port without the Lo (-) silk screen under the differential pressure
sensor, and route the hose through the top of the cabinet to the supply air pipe plenum chamber.
(There should be two binding points adjacent to the pressure inlet. The distance between the
binding point closer to the pressure inlet and the pressure inlet should not exceed 25 mm, and the
distance between two binding points is within 20–30 mm.)
3. Connect cables to the differential pressure sensor.
4. After powering on the NetCol8000, choose Settings > System Settings > Indoor Fan, and set Air-
side difference pressure sensor type to 0–500 Pa.
Downflow
Upflow
13