Synchronous playback of GX Works3 and GX LogViewer
Check which one of the four error causes has caused the error.
Operating procedure
1.
Start the offline monitoring. (Page 51 OFFLINE MONITOR FUNCTION)
2.
Double-click "File Saving Trigger Establishment" in the event history to open the program of the file saving trigger
establishment condition.
At this time, one of the four devices that are a condition of the error device cannot be determined.
Error cause
3.
To determine the cause, display the waveform data in GX LogViewer.
Select a device/label  Right-click  [Wave Display]
Set file saving trigger
Select a device/label
to be displayed in
a waveform.
7 OPERATION EXAMPLE
7.1 How to Check the Recording Result
7
64