Dnp Point Map Notes - GE Multilin EPM 6000 Instruction Manual

Multi-function power meter
Hide thumbs Also See for Multilin EPM 6000:
Table of Contents

Advertisement

5.2.2

DNP Point Map Notes

5–12
1.
Responds to Function 5 (direct operate), Qualifier Code 7 or 8, Control Code 3, Count 0,
On 1 ms, Off 0 ms ONLY.
2.
Responds to Function 6 (direct operate - no acknowledge), Qualifier Code 7, Control
Code 3, Count 0, On 1 ms, Off 0 ms ONLY.
(n–d)
3.
The multiplier = 10
6 per energy format scale and d = number of decimal places.
4.
Example: If energy format = 7.2 K and watt-hours counter = 1234567, with n=3 (k-
scale) and d = 2 (2 digits after decimal point), then multiplier = 10
energy is 1234567 × 10 Wh, or 12345.67 kWh.
5.
Values greater than 150 V secondary read 32767.
6.
Values greater than 300 V secondary read 32767.
7.
Values greater than 10 A secondary read 32767. For the 1 A model, the multiplier is (2/
32768) and values above 2 A secondary read 32767.
8.
CT ratio = (numerator × multiplier) / denominator.
9.
PT ratio = (numerator × multiplier) / denominator.
10. Clear via Function 2 (write), Qualifier Code 0.
, where n and d are derived from the energy format. n = 0, 3, or
EPM 6000 MULTI-FUNCTION POWER METERING SYSTEM – USER GUIDE
CHAPTER 5: COMMUNICATIONS
(3–2)
= 10, so the