6.5. Register Map
6.5.1. RMS Total/Average Block
•
Start Address: 3000
•
Block Size: 20 Registers
•
Modbus Read Function Code: 03
•
Always transfer the Whole Block.
Add
Parameters
ress
3000
VA
3002
W
3004
VAR
3006
PF
3008
VLL
3010
VLN
3012
A
3014
F
3016
RESERVED1
3018
INTR
6.5.2. RMS Phase A Block
•
Start Address: 3030
•
Block Size: 20 Registers
•
Modbus Read Function Code: 03
•
Always transfer the Whole Block.
Addr
Parameters
ess
3030
VA
A
3032
W
A
3034
VAR
A
3036
PF
A
3038
V
AB
3040
V
A
3042
A
A
3044
F
A
3046
RESERVED2
3048
INTR
A
GE Multilin
Description
Total RMS Apparent Power
Total RMS Active Energy
Total RMS Reactive Energy
Total RMS PF
Total RMS Line to Line Voltage
Total RMS Line to Neutral Voltage
Total RMS Current
Total RMS Frequency
Reserved for future use
Number of Power Interruptions
Description
RMS Phase A Apparent Power
RMS Phase A Active Energy
RMS Phase A Reactive Energy
RMS Phase A PF
RMS Phase A Line to Line Voltage
RMS Phase A Line to Neutral
Voltage
RMS Phase A Current
RMS Phase A Frequency
Reserved for future use
Number of Power Interruptions
Sub Meters
Data Type
32-bit Float
32-bit Float
32-bit Float
32-bit Float
32-bit Float
32-bit Float
32-bit Float
32-bit Float
32-bit Unsigned Long
32-bit Unsigned Long
Data Type
32-bit Float
32-bit Float
32-bit Float
32-bit Float
32-bit Float
32-bit Float
32-bit Float
32-bit Float
32-bit Unsigned Long
32-bit Unsigned Long
47