Mitsubishi Electric Y Series Manual page 83

Hide thumbs Also See for Y Series:

Advertisement

WR2-Series
PQRY-P YLM-A1
Model
Power source
Cooling capacity
*1
kW
(Nominal)
kcal / h
*1 BTU / h
Power input
kW
Current input
A
EER
kW / kW
Temp. range of
Indoor
W.B.
cooling
Inlet water
°C
Heating capacity
*2
kW
(Nominal)
kcal / h
*2 BTU / h
Power input
kW
Current input
A
COP
kW / kW
Temp. range of
Indoor
D.B.
heating
Inlet water
°C
Indoor unit
Total capacity
connectable
Model / Quantity
Sound pressure level
dB <A>
(measured in anechoic room)
Sound power level
dB <A>
(measured in anechoic room)
Refrigerant piping High pressure
mm (in.)
diameter
Low pressure
mm (in.)
Circulating water Water flow rate
m
3
/ h
L/min
cfm
Pressure drop
kPa
Operating
3
m
/ h
volume range
Compressor
Type
Starting method
Motor output
kW
Case heater
kW
External finish
External dimension HxWxD
mm
in.
Protection
High pressure protection
devices
Inverter circuit (COMP.)
Compressor
Refrigerant
Type x original charge
Net weight
kg (lbs)
Heat exchanger
Water volume in
L
plate
Water pressure
MPa
Max.
Optional parts
Notes:
*1,*2 Nominal conditions
Indoor
27ºCD.B./19ºCW.B.
Cooling
(81ºFD.B./66ºFW.B.)
Heating
20ºCD.B. (68ºFD.B.)
*The ambient temperature of the heat source unit needs to be kept below 40ºCD.B.
*The ambient relative humidity of the heat source unit needs to be kept below 80%.
*The heat source unit should not be installed at outdoor.
*Be sure to mount a strainer (more than 50 meshes) at the water inlet piping of the unit.
*Be sure to provide interlocking for the unit operation and water circuit.
*Nominal condition *1,*2 are subject to JIS B8615-2.
*Due to continuing improvement, above specification may be subject to change without notice.
PQRY-P350YLM-A1
3-phase 4-wire 380-400-415 V 50/60 Hz
40.0
35,000
136,500
7.14
12.0-11.4-11.0
5.60
15.0~24.0°C (59~75°F)
10.0~45.0°C (50~113°F)
45.0
40,000
153,500
7.53
12.7-12.0-11.6
5.97
15.0~27.0°C (59~81°F)
10.0~45.0°C (50~113°F)
50~150% of heat source unit capacity
P10~P250/1~35
52
66
22.2 (7/8) Brazed
28.58 (1-1/8) Brazed
7.20
120
4.2
44
4.5 ~ 11.6
Inverter scroll hermetic compressor
Inverter
9.5
Galvanized steel sheets
1,450 x 880 x 550
57-1/8 x 34-11/16 x 21-11/16
High pressure sensor, High pressure switch
at 4.15 MPa (601 psi)
Over-heat protection, Over-current protection Over-heat protection, Over-current protection Over-heat protection, Over-current protection
Over-heat protection
R410A x 6.0 kg (14 lbs)
217 (479)
plate type
5.0
2.0
Joint: CMY-Y102SS/LS-G2, CMY-R160-J1
Inlet water temperature
30ºC (86ºF)
7.5m (24-9/16ft.)
20ºC (68ºF)
PQRY-P400YLM-A1
3-phase 4-wire 380-400-415 V 50/60 Hz
45.0
40,000
153,500
8.03
13.5-12.8-12.4
5.60
15.0~24.0°C (59~75°F)
10.0~45.0°C (50~113°F)
50.0
45,000
170,600
8.37
14.1-13.4-12.9
5.97
15.0~27.0°C (59~81°F)
10.0~45.0°C (50~113°F)
50~150% of heat source unit capacity
P10~P250/1~40
52
66
22.2 (7/8) Brazed
28.58 (1-1/8) Brazed
7.20
120
4.2
44
4.5 ~ 11.6
Inverter scroll hermetic compressor
Inverter
10.7
Galvanized steel sheets
1,450 x 880 x 550
57-1/8 x 34-11/16 x 21-11/16
High pressure sensor, High pressure switch
at 4.15 MPa (601 psi)
Over-heat protection
R410A x 6.0 kg (14 lbs)
217 (479)
plate type
5.0
2.0
Joint: CMY-Y102SS/LS-G2, CMY-R160-J1
Pipe length
Level difference
0m (0ft.)
SPECIFICATIONS
PQRY-P450YLM-A1
3-phase 4-wire 380-400-415 V 50/60 Hz
50.0
45,000
170,600
9.29
15.6-14.8-14.3
5.38
15.0~24.0°C (59~75°F)
10.0~45.0°C (50~113°F)
56.0
50,000
191,100
9.79
16.5-15.7-15.1
5.72
15.0~27.0°C (59~81°F)
10.0~45.0°C (50~113°F)
50~150% of heat source unit capacity
P10~P250/1~45
54
70
22.2 (7/8) Brazed
28.58 (1-1/8) Brazed
7.20
120
4.2
44
4.5 ~ 11.6
Inverter scroll hermetic compressor
Inverter
11.6
Galvanized steel sheets
1,450 x 880 x 550
57-1/8 x 34-11/16 x 21-11/16
High pressure sensor, High pressure switch
at 4.15 MPa (601 psi)
Over-heat protection
R410A x 6.0 kg (14 lbs)
217 (479)
plate type
5.0
2.0
Joint: CMY-Y102SS/LS-G2, CMY-R160-J1
83