On/Off; Functions; Specifications - Mitsubishi Electric G-50A Instruction Book

Central controller
Hide thumbs Also See for G-50A:
Table of Contents

Advertisement

3. Functions

3 - 1 Specifications

Item
Source power requirement
Environmental condition
Dimensions
Weight
System condition
Number of control unit
User operating function

ON/OFF

Operation
mode
Fan speed *1
Operation
Air direction
and swing
operation *1
Temperature
setting
DC24V, 0.02A (Maximum loading)
Power received from PAC-SC50KUA Power Supply Unit via M-NET transmission
line, or from an R410A compatible CITY MULTI outdoor unit (except the S Series).
*Note: While the power to the connected outdoor unit is turned off, the
Input voltage
DC12V, 0.2A (Maximum loading)
Power is received from the PAC-SC50KUA Power Supply Unit via the DC power line.
Operating
Temperature
Non operating
Humidity
30 ~ 90%RH (No condensation)
120 (H) × 300 (W) × 80 [*19] (D)
mm
4-3/4 (H) × 11-13/16 (W) × 3-1/8 [*3/4] (D)
in
kg
1.0
lb
2-1/4
Indoor unit or independent OA processing unit or LOSSNAY
: 50 units maximum (50 groups maximum)*3
Number of units (indoor or independent OA processing unit or LOSSNAY) in one group
: 1-16 units
*Note Indoor unit, independent OA processing unit and LOSSNAY can not regis-
ter to the same group.
Number of remote controllers in one group
: 1-2
Number of system controllers in one group
: 0-4 (including the number of remote controller in one group)
: 0-3 for groups which have one remote controller.
Number of indoor units interlocked with one OA processing unit or LOSSNAY
: 0-16 (some types of OA processing unit can only be operated when inter-
The ON/OFF operation can be performed as a collective or per group.
The switch operation for the operation mode setting can be performed as a collective or
per group.
[Selectable operation mode for the indoor unit]
COOL/DRY/FAN/AUTO/HEAT
*1
[Selectable operation mode for the independent ventilation]
HEAT RECOVERY/BY-PASS/AUTO
The switch operation to set the High and Low speed can be performed as a collective or
per group.
(The 4 fan speed setting is available to the indoor that has 4 levels)
(Fan speed is settable to AUTO on the indoor units that support that setting via G-50A of
ver. 3.10 or later.)
The air flow direction can be switched to 4 directions and swing operation as a collec-
tive or per group.
(Airflow setting can be switched to "5 directions" or to "AUTO" on the indoor units that
support those settings via G-50A of ver. 3.10 or later.)
Temperature setting can be performed collectively or per group.
[Setting temperature range]
Cool (Dry) operation
Heat operation
Auto operation
Specification
G-50A cannot perform a schedule operation, collect charge
data, or perform energy save control.
0˚C ~ +40˚C / 32˚F ~ +104˚F
– 20˚C ~ +60˚C / – 4˚F ~ +140˚F
locked to a maximum of 9 units)
: 19 ~ 30˚C / 67 ~ 87˚F
: 17 ~ 28˚C / 63 ~ 83˚F
: 19 ~ 28˚C / 67 ~ 83˚F
– 4 –
*[
]: indicate the thickness from
the wall.