No.F002 Fire Extinguishing System Conceptual Diagram 2
-
+
E
+
ROV SIL
AL
AUX
REMOTE
24V
CONTROL
Technical requirements:
1.
All fire extinguishing signal cables are red (BOM number: 25030029) and black (BOM number: 25030073) cables ;The red cable is positive and the black cable is negative. The pneumatic switch, Warning
signs, and fire alarm bell each has two wiring terminals that connect to two wires. The fire alarm bell is polarity insensitive. For details, see the diagram.
2.Connect the Smoke Detector,Heat Detector,Horn Storbes,Fire Alarm Bell and Start/Stop Button to the UT terminal (14170025). Cord end terminals (14170214) are used to connect other fire
devices and extinguishing control panels host terminals.
3.Connect a 10K terminal resistor to each of the last the fire alarm sounder and fire alarm horn/strobe in parallel.
4.Connect cables to the smoke detector and heat detector by referring to the diagram. Connect a 6.8 K terminal resistor to the last smoke and heat detectors in parallel.
5.Connect the emergency abort button and pneumatic switch to a 6.8 K terminal resistor in parallel, and to a 470 ohm resistor in serial. Connect an electrical actuator to a 1N4004 diode in
parallel.
6.Alarm signals are reported to the monitoring system over shielded straight-through network cables. The connection definitions are as follows: LOCAL FIRE, FIRE RELAY, and FAULT
RELAY. The signal cables connect to the ECC over dry contacts.
7.Attach cable labels to all cables connected to the extinguishant control panel and wiring terminals on electrical actuators and pneumatic switches. See the label table for the label content.
Cable direction labels must be arranged neatly in the same direction. Cables must be bound neatly, with cable ties in the same direction. (Labels are printed on label paper with the BOM
number 29041061, attached on cable ties with the BOM number 21200708, and bound to corresponding cables.)
Smoke Detector-1
Smoke Detector-2
red
red
L1 IN
L1 IN
-R
red
L1 OUT
L1 OUT
L2
L2
black
black
Heat Detector-1
Heat Detector-2
red
L1 IN
-R
red
L1 OUT
L2
black
black
red
black
red
black
FLT RST
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
DATA
POWER
ZONE 1
ZONE 2
ZONE 3
2ND
NAC1
NAC2
STATUS UNITS
SOUNDER
Connect the first
Connect smoke
Connect heat
Data cable
Power cable
stage alarm to the
detector in
detector in
Connect the second stage alarm to
fire alarm bell.
detection zone 1
detection zone 2
the horn strobes and warning signs .
Terminal Resistor(6.8K)
-R
red
L1 IN
Terminal Resistor(6.8K)
-R
L1 OUT
L2
-
NC
C
No
NC
C
NO
+
-
+
-
+
-
+
-
+
-
+
1ST
2ND
MODE
MAN
ABORT
REL
EXTING
LOW
STAGE
STAGE
SELECT
RELEASE
PRESS
PRESS
SWITCH
SWITCH
Connect the
Connect the pressure
Connect the electrical
emergency
actuator drive signal to the
signal to the pneumatic
abort port to
switch.
electrical actuator.
the Extinguishant
abort button .
To Monitoring system
brown & white
green
brown & white
brown & white
green
green
-
NO
C
NC
C
NO
NC
C
NO
NC
C
NO
EXTRACT
TROUBLE
LOCAL
FIRE
RELAY
FIRE
RELAY
Connect the fault signal
Connect the gas release
Connect the fire alarm
signal output (NO) to the
output (NO) to the
signal output (NO) to the
collector of the monitoring
collector of the monitoring
collector of the monitoring
system.
system.
system.