No.P002 Power Supply and Distribution System
HUAWEI SCOPE
BBB-1250A-A1
Module 1 400kVA Extensible 600kVA
50kVA
50kVA
50kVA
50kVA
50kVA
50kVA
BBB-1250A-A2
50kVA
50kVA
50kVA
50kVA
50kVA
50kVA
SMDB-A1
PM1
QF1
16A/4P
MCCB
UPS5000E-A1
800K
1L11~1L13,1N
PM2
PM3
PM4
PM5
PM5
QF2
QF3
QF4
QF5
QF5
400A/4P
400A/4P
400A/4P
400A/4P
400A/4P
MCCB
MCCB
MCCB
MCCB
MCCB
rPDU-A
rPDU-B
UPS5000E-B1
800K
Module 1 400kVA Extensible 600kVA
50kVA
50kVA
50kVA
50kVA
50kVA
50kVA
50kVA
50kVA
50kVA
50kVA
50kVA
50kVA
1FU1~3
SMDB-B1
POWER DB-1
PM4
PM3
PM2
PM1
QF4
QF3
QF2
QF1
400A/4P
400A/4P
400A/4P
16A/4P
MCCB
MCCB
MCCB
MCCB
Diagram
BBB-1250A-B1
BBB-1250A-B2
NC
12
12
COM
NO
11
14
14
11
1FS
1QFS
2QFS
Imax:40kA
32A/4P MCB
32A/4P MCB
1HR
1HG
1HY
FU1~3
FU4~6
1L11~1L13,1N
2L11~2L13,2N
ATS 160A/4P
FU10
L21,N
Power
FU7~9
Voltage
L21~L23,N
Power Meter
Current
TA1~TA3
200/5A 0.5
QF13
QF12
QF11
QF10
QF9
QF8
QF7
QF6
10A/2P
10A/2P
10A/2P
10A/2P
10A/2P
10A/2P
10A/2P
16A/2P
YO+AUX
30mA RCD
30mA RCD
30mA RCD
30mA RCD
30mA RCD
30mA RCD
30mA RCD
30mA RCD
NC
NO
COM
2FS
Imax:40kA
2HY
2HG
2HR
QF5
QF4
QF3
QF2
QF1
16A/2P
16A/2P
63A/4P
63A/4P
63A/4P
30mA RCD
30mA RCD
MCB
MCB
MCB

Advertisement