Category
Output Settings
Bypass Settings
Setting
Battery Settings
Parameter
Output voltage level(V)
Output volt.
adjustment(V)
Output frequency (Hz)
Output freq.track rate (Hz/s)
EOD restart
EOD restart delay (min)
Maximum bypass
voltage level is 400 V
voltage
Bypass voltage lower limit
Bypass frequency range (Hz)
Battery type
Single battery voltage(V)
Singe battery capacitty(Ah)
Batteries in a battery string
Number of battery strings
Installation time
Maintenance period (d)
Cell floatvoltage (V/cell)
Cell equalizedvolt. (V/cell)
Default Value
400 V
The default value is 220.0, 230.0,
and 240.0 when the voltage level
is 380 V, 400 V, and 415 V
espectively.
50 Hz
0.6 Hz/s
Enable
10
+15%
-20%
±2 Hz
VRLA batt.
12
Depends on
the actual
model.
The default
value depends
on the model.
1
-
0
2.25
2.35
Value Range
Setting
380 V, 400 V, 415 V
400 V
380 V: 209.0–
231.0
400 V: 218.5–
230
241.5
415 V: 228.0–
252.0
50 Hz, 60 Hz
50 Hz
0.1 Hz/s–2.0 Hz/s
0.6Hz/s
Disable, Enable
Enable
1–1440
10
+10%, +15%, +20%
Default value
-10%, -15%, -
20%, -30%, -
Default value
40%, -50%, -
60%
±0.5 Hz to ±
Default value
6 Hz
VRLA batt.,
lithium batt.
lithium batt.
2V/6V/12V
64
5–9999
40
The value
range depends
16
on the model.
1–6
5
Battery installation
-
time
0–365
120
2.23–2.30
2.25
2.30–2.40
2.35