Huawei FusionDC1000A Quick Manual page 15

Prefabricated all-in-one data center
Hide thumbs Also See for FusionDC1000A:

Advertisement

No.S003 Pre-fab. Module Grounding Position Diagram
1374
A
Bolt assembly
M12X30
Note:
Four external ground points are set for each container and are set at the bottom of the rear
wall. You can select a ground point based on the site requirements and connect the ground
point to the ground grid. Before grounding, remove the tin foil. The ground bolt is a M12x25
stainless steel hexagon bolt. Tighten the ground bolt with a torque of 470. (Torque range:
±10%)/(Unit: Kgf.cm).
1
A
No.
A part
Enlarged at
10:1
Container
ground
point
GB9074_17-88_M12X30_S
Drawing No./Code
A
A
Bolt assembly M12X30
16
Qty
Item