10. Use of High-speed Counters

10.1

Outline

High-speed counters use input terminals (X000 to X007) of the main unit for inputs, and offer counting up to
60 kHz (1-phase).
Input terminals not used for high-speed counters are available for general-purpose inputs.
10.2

Types of Counting and Operations

The main unit has built-in 32-bit high speed bi-directional counters (1-phase 1-count input, 1-phase 2-count
input and 2-phase 2-count input).
For some high-speed counters, external reset input terminals or external start input terminals (start of
counting) can be selected.

10.2.1 Types and input signal forms

The types and input signals (waveforms) of high-speed counters (1-phase 1-count input, 1-phase 2-count
input and 2-phase 2-count input) are shown below.
High-speed
counter type
1-phase 1-count
input
1-phase 2-count
input
2-phase 2-count
input

10.2.2 High-speed counter device notations

The input terminal assignments for FX
combination with a special auxiliary relay. This section classifies these high-speed counter devices under the
following notations. Note that an "(OP)" input cannot be programmed.
Standard device numbers
C248
C253

10.2.3 Cautions in connecting mating device

Encoders with the output forms in the following table can be connected to the input terminals. (The encoders
may not function correctly depending on electrical compatibility. Check the specifications in advance.)
Voltage output type encoders and absolute encoders cannot be connected to the high-speed counter input
terminals.
Input terminals of main unit
86
Input signal form
UP/DOWN
+1
+1
UP
DOWN
A-phase
+1
+1
B-phase
Up-counting
Switched device numbers
C248 (OP)
C253 (OP)
Terminals for connecting
→ For the input specifications, refer to Section 4.3.
Down-count or up-count is specified by turning on or off
M8235 to M8245.
ON : Down-counting
OFF: Up-counting
Up-count or down-count
The counting direction can be checked with M8246 to M8250.
ON : Down-counting
-1
-1
OFF: Up-counting
Automatic up-count or down-count according to change in
input status of phase A/B
-1
-1
The counting direction can be checked with M8251 to M8255.
ON : Down-counting
Down-counting
OFF: Up-counting
PLC high-speed counters can be switched when used in
3S
Output form that can be directly connected
Open collector transistor output form (applicable to 24 V DC)
10 Use of High-speed Counters