FX
Series Programmable Controllers
3S
User's Manual - Hardware Edition

12.2.4 Example of external wiring

1. Transistor output (Sink)
100 to 240 V AC
Breaker
Power ON
PL
MC
MC
Emergency
MC
+
Power supply for load
connected to PLC output
For details on emergency
stop operation, refer to
"DESIGN PRECAUTIONS"
at "Safety Precautions" field.
*1.
The output circuit of this PLC does not have a built-in fuse.
Provide a fuse suitable to each load to prevent blowout of the wires on the circuit board caused by
output element fracture due to load short-circuiting.
*2.
"•" represents vacant terminals.
WIRING PRECAUTIONS
Do not wire the vacant terminals externally.
Doing so may damage the product.
116
stop
MC
DC power supply
12.2 External Wiring of Transistor Output (Sink/Source) Type
Fuse
*1
COM0
Y000
Load
COM1
Y001
*1
Fuse
COM2
Y002
Y005
Load
*2
12 Output Wiring Procedures
Main unit
transistor output (sink)