SmartACBox 12-In 1-Out Smart AC Combiner Box
User Manual
Step 6 Set NetEco parameters to ensure that a connection is set up between the SmartLogger1000
and the NMS.
1.
Issue 03 (2018-05-15)
Figure 6-7 Adding devices
b.
Click Add Devices.
Log in as Advanced User. On the Settings tab page, choose Comm. Param. > NetEco
to set NetEco parameters and upload the security certificate.
Figure 6-8 Setting NetEco parameters
NetEco server: IP address for the NMS server
Port number: If Huawei NMS is connected, set this parameter to 16100 by default. If a third-party
NMS is connected, set this parameter to the number of the service port opened by the system.
Address mode: Select Comm. Address or Logical Address. If the devices connected to the three
RS485 ports on the SmartLogger have duplicate addresses, Logical Address must be selected.