Figure 3-23 Setting the multi-speed function
P4-00
P4-01
P4-02
P4-03
P4-04
P4-05
P4-06
P4-07
P4-08
P4-09
In the preceding figure, DI7, DI4, DI8, and DI2 are used as the multi-frequency input terminals,
each of which has a bit value. The state combinations of these terminals correspond to multiple
each of which has a bit value. The state combinations of these terminals correspond to multiple
frequencies, When (DI7, DI4, DI8, DI2) = (0, 0, 1, 0), the state combination value is 2,
frequencies, When (DI7, DI4, DI8, DI2) = (0, 0, 1, 0), the state combination value is 2,
corresponding to the value set in PC-02. The target running frequency is automatically calculated
by PC-02 x P0-10.
The PE6000 supports a maximum of four DI terminals to be used as the multi-frequency input
terminals. You can also use less than four DI terminals, and the empty bit is considered to be 0.
3.7.9 Setting the Motor Rotating Direction
After the AC drive restores the default settings, press RUN to drive the motor to rotate. In this
After the AC drive restores the default settings, press RUN to drive the motor to rotate. In this
case, the rotating direction is regarded as the forward rotation. If the rotating direction is reverse
to the direction required by the equipment, power off the AC drive and exchange any two of the
to the direction required by the equipment, power off the AC drive and exchange any two of the
output UVW cables (wait until the main capacitor of the AC drive is completely discharged).
output UVW cables (wait until the main capacitor of the AC drive is completely discharged).
In some applications where both forward rotation and reverse rotation are required, enable
the reverse control (P8-13 = 0, default value) and meanwhile reverse the rotating direction by
setting P0-09 to 1. Then press RUN to make the motor rotate in the reverse direction, as shown in
09 to 1. Then press RUN to make the motor rotate in the reverse direction, as shown in
the following figure.
02. The target running frequency is automatically calculated
forward rotation and reverse rotation are required, enable
13 = 0, default value) and meanwhile reverse the rotating direction by
Operation, Display and Application Examples
Operation, Display and Application Examples
PC-00
PC-01
PC-02
...
PC-14
PC-15
x (P0-10)
rminals, and the empty bit is considered to be 0.
If the rotating direction is reverse
33
P0-07 = 0
P0-27 = 0
P0-03 = 6
frequency input terminals,