Description of Function Codes
corresponding setting. When the analog input voltage exceeds the maximum value (P4- 15), the
maximum value is used. When the analog input voltage is less than the minimum value (P4-13),
the value set in P4-34 (Setting for AI less than minimum input) is used.
When the analog input is current input, 1mA current corresponds to 0.5 V voltage.
P4-17 (AI1 filter time) is used to set the software filter time of AI1. If the analog input is liable to
interference, increase the value of this parameter to stabilize the detected analog input. However,
increase of the AI filter time will slow the response of analog detection. Set this parameter properly
based on actual conditions
In different applications, 100% of analog input corresponds to different nominal values. For
details, refer to the description of different applications.
Two typical setting examples are shown in the following figure.
Figure 5-10 Corresponding relationship between analog input and set values