6 - Power protections
List
The Power protections, available by default for Ekip Hi-Touch, Ekip G Touch, Ekip G-Hi Touch models and configurable in Ekip Touch as additional
SW package, are:
Name
Type of protection
RP
Reverse active power
D
Directional short-circuit with adjustable delay
(2)
OQ
Maximum reactive power
(1)
OP
Active overpower
(1)
UP
Active underpower
(1)
RQ
Reverse reactive power
(1)(2)
Cos φ
Minimum Cos φ
Further details about the protections are given in document 1SDH001330R1002.
(1)
the protection is not available by default with Ekip Hi-Touch. However, it can be integrated by requesting the relative SW package
(2)
the protection is not available by default with Ekip G Touch. However, it can be integrated by requesting the relative SW package
(3)
Block configuration available via Ekip Connect
(4)
Directional Zone Selectivity functions as an alternative to Zone Selectivity S and G
WARNING! The Power flow parameters effect the sign of the power and power factor values measured by the unit.
Power flow must be configured and verified on the basis of your installation to ensure that all the protections of the
Power Protections package function correctly
Summary table
ABB
ANSI
(7)
Threshold
P11 = -1...-0,05 Sn step = 0,001
RP
32R
Sn
I7 Fw/Bw = 0,6...10 In step = 0,1
D
67
(8)
In
OQ
32OF
Q27 = 0,4...2 Sn step = 0,001 Sn
OP
32OF
P26 = 0,4...2 Sn step = 0,001 Sn
UP
32LF
P23 = 0,1...1 Sn step = 0,001 Sn
(9)
Q24 = -1...-0,1 Sn step = 0,001
RQ
40 / 32R
Sn; Kq = -2...2 step = 0,01; Vmin
= 0,5...1,2 Un step = 0,01
Cos φ 78
Cos φ = 0,5...0,95 step = 0,01
(5)
calculation of t
is valid for values which have exceeded the trip threshold of the protection
t
(6)
tolerance values valid with Trip unit supplied at full rate or by auxiliary power supply, trip time ≥ 100 ms, temperature and current values within
operating limits; the tolerance value is ± 20% if the conditions are not guaranteed
(7)
ANSI / IEEE C37-2 codification
(8)
the protection does not detect the fault current direction for < 5 V voltages.
(9)
not active if the circuit-breaker is open (TRIP OFF is signaled); the protection is also active for negative active power, but is independent of RP
protection (Protection from inverse active power)
35 | © 2019 ABB | 1SDH001316R1002 - ECN000086501 - Rev. A
Threshold
Time
Tolerance
Time
threshold
t11 = 0,5...100 s
± 10 %
step = 0,1 s
t7 Fw/Bw =
± 7 % If ≤ 6 In
0,1...0,8 s step
± 10 % If > 6 In
= 0,01 s
t27 = 0,5...100 s
± 10 %
step = 0,5 s
t26 = 0,5...100 s
± 10 %
step = 0,5 s
t23 = 0,5...100 s
± 10 %
step = 0,5 s
t24 = 0,5...100 s
± 10 %
step = 0,5 s
Additional functions
(3)
Trip enable, Block
Trip enable, Directional Zone Selectivity
enable, Block, Direction Min Angle
Trip enable, Block
Trip enable, Block
Trip enable, Block, Startup enable
Trip enable, Block
Calculation
formula
Tolerance t
(6)
t
t
(5)
t
The best of the two values: ± 10% or
t
= t11
± 40 ms (for set time < 5 s) / ± 100
t
ms (for set time ≥ 5 s)
± 40 ms (for t7 ≥ 400 ms) / whichever
t
= t7
is higher, ± 20 ms or ± 10 % (for t7 <
t
400 ms)
The best of the two values: ± 10% or
t
= t27
± 40 ms (for set time < 5 s) / ± 100
t
ms (for set time ≥ 5 s)
The best of the two values: ± 10% or
t
= t26
± 40 ms (for set time < 5 s) / ± 100
t
ms (for set time ≥ 5 s)
The best of the two values: ± 10% or
t
= t23
± 40 ms (for set time < 5 s) / ± 100
t
ms (for set time ≥ 5 s)
The best of the two values: ± 10% or
t
= t24
± 40 ms (for set time < 5 s) / ± 100
t
ms (for set time ≥ 5 s)
Protections | 6 - Power protections
ABB | SACE Emax 2
, Startup
(4)
Continued on the next page