4.3.3

IP communication test

When the IP packet transfer function is used, whether no error occurs in the communication route within CC-Link IE
Field Network is checked. The following can be checked using the IP communication test:
• Cables are properly connected on the communication route.
• Parameters related to the IP packet transfer function, such as an IP address and routing parameters, are
correctly set on the communication route.
• If a CPU module or a CC-Link IE Controller Network module that does not support the IP packet transfer
function is connected in the communication route.
The following system configuration is used to explain the procedure of the IP communication test.
192.168.1.1
Ethernet device
(request source
device)
The IP communication test allows the communication paths in the dotted line above to be checked.
RESET
CPU module 1: 192.168.1.10
Control station (Station No.1):
192.168.2.1
Network No.1
or
power OFF
ON
CPU module 2: 192.168.10.10
Normal station (station No.2):
192.168.2.2
Network No.2
Network No.10
1.
Set parameters for the CPU module and CC-Link IE
Controller Network module. (
4.3.2 (2))
2.
Write the set parameters to the CPU module using
GX Works2.
[Online]
[Write to PLC]
3.
Reset the CPU module or power off and on the
system.
4.
Open the "IP Communication Test" window. Enter
the IP address of the CPU module 2 or the normal
station (station No.2) connected to the request
destination device in "Communication Target".
[Diagnostics]
CHAPTER 4 FUNCTIONS
192.168.10.1
Ethernet device
(request destination
device)
Page 111, Section
[CC IE Field Diagnostics]
button
113
4