Appendix B - Parameter Settings; Default Settings - ABB ACS 600 Supplement To Firmware Manual

Standard application program 5.0; master/follower application macro
Hide thumbs Also See for ACS 600:
Table of Contents

Advertisement

Default Settings

Suitable for a Speed-Controlled
Master after Group 99 and
Parameter 60.01 are set.
99 START-UP DATA
⇒ ENGLISH
99.01 LANGUAGE
99.02 APPLICATION MACRO ⇒ M/F CTRL
99.03 APPLIC RESTORE
NO
99.04 MOTOR CTRL MODE
DTC
⇒ 0 V
99.05 MOT NOM VOLTAGE
99.06 MOTOR NOM CURRENT⇒ 0.0 A
⇒ 50.0 Hz
99.07 MOTOR NOM FREQ
⇒ 1 rpm
99.08 MOTOR NOM SPEED
⇒ 0.0 kW
99.09 MOTOR NOM POWER
⇒ NO
99.10 MOTOR ID RUN
10 START/STOP/DIR
10.01 EXT1 STRT/STP/DIR
DI1,2
10.02 EXT2 STRT/STP/DIR
DI1,2
10.03 DIRECTION
REQUEST
11 REFERENCE SELECT
11.01 KEYPAD REF SELECT
REF1 (rpm)
11.02 EXT1/EXT2 SELECT
DI3
11.03 EXT REF1 SELECT
AI1
11.04 EXT REF1 MINIMUM
0 rpm
11.05 EXT REF1 MAXIMUM
1500 rpm
11.06 EXT REF2 SELECT
AI2
11.07 EXT REF2 MINIMUM
0%
11.08 EXT REF2 MAXIMUM
100%
12 CONSTANT SPEEDS
12.01 CONST SPEED SEL
DI4(SPEED4)
12.02 CONST SPEED 1
300 rpm
12.03 CONST SPEED 2
600 rpm
12.04 CONST SPEED 3
900 rpm
12.05 CONST SPEED 4
300 rpm
12.06 CONST SPEED 5
0 rpm
12.07 CONST SPEED 6
0 rpm
12.08 CONST SPEED 7
0 rpm
12.09 CONST SPEED 8
0 rpm
12.10 CONST SPEED 9
0 rpm
12.11 CONST SPEED 10
0 rpm
12.12 CONST SPEED 11
0 rpm
12.13 CONST SPEED 12
0 rpm
12.14 CONST SPEED 13
0 rpm
12.15 CONST SPEED 14
0 rpm
12.16 CONST SPEED 15
0 rpm
13 ANALOGUE INPUTS
14 RELAY OUTPUTS
15 ANALOGUE OUTPUTS
Refer to the Firmware Manual, Appendix B.
16 SYSTEM CONTR INPUTS
16.01 RUN ENABLE
DI6
16.02 PARAMETER LOCK
OPEN
16.03 PASS CODE
0
16.04 FAULT RESET SEL
NOT SEL
16.05 USER MACRO IO CHG
NOT SEL
16.06 LOCAL LOCK
OFF
16.07 PARAM SAVE
DONE
20 LIMITS
21 START/STOP
Refer to the Firmware Manual, Appendix B.
22 ACCEL/DECEL
22.01 ACC/DEC 1/2 SEL
DI5
22.02 ACCEL TIME 1
3.00 s
22.03 DECEL TIME 1
3.00 s
22.04 ACCEL TIME 2
60.00 s
22.05 DECEL TIME 2
60.00 s
22.06 ACC/DEC RAMP SHPE
0.00 s
22.07 EM STOP RAMP TIME
3.00 s
ACS 600 Master/Follower Application Macro
Appendix B – Parameter Settings
23 SPEED CTRL
Refer to the Firmware Manual, Appendix B.
24 TORQUE CTRL
24.01 TORQ RAMP UP
0.00 s
24.02 TORQ RAMP DOWN
0.00 s
25 CRITICAL SPEEDS
Refer to the Firmware Manual, Appendix B.
26 MOTOR CONTROL
26.01 FLUX OPTIMIZATION
NO
26.02 FLUX BRAKING
YES
*26.03 IR COMPENSATION
0.0%
30 FAULT FUNCTIONS
30.01 AI<MIN FUNCTION
FAULT
30.02 PANEL LOSS
FAULT
30.03 EXTERNAL FAULT
NOT SEL
30.04 MOTOR THERM PROT
NO
30.05 MOTOR THERM P MODE
DTC
30.06 MOTOR THERM TIME
(calculated)
30.07 MOTOR LOAD CURVE
100.0%
30.08 ZERO SPEED LOAD
74.0%
30.09 BREAK POINT
45.0 Hz
30.10 STALL FUNCTION
FAULT
30.11 STALL FREQ HI
20.0 Hz
30.12 STALL TIME
20.00 s
30.13 UNDERLOAD FUNC
NO
30.14 UNDERLOAD TIME
600.0 s
30.15 UNDERLOAD CURVE
1
30.16 MOTOR PHASE LOSS
NO
30.17 EARTH FAULT
FAULT
30.18 COMM FAULT FUNC
FAULT
30.19 COMM FAULT TIMEOUT
1.00 s
30.20 COMM FAULT RO/AO
ZERO
31 AUTOMATIC RESET
32 SUPERVISION
33 INFORMATION
34 PROCESS SPEED
50 ENCODER MODULE
Refer to the Firmware Manual, Appendix B.
51 COMMUNICATION MODULE
Visible only with a communication module active.
Refer to the module manual.
60 MASTER/FOLLOWER
**60.01 MASTER LINK MODE ⇒ NOT IN USE
60.02 TORQUE SELECTOR
TORQUE
60.03 WINDOW SEL ON
NO
60.04 WINDOW WIDTH POS
0.0 rpm
60.05 WINDOW WIDTH NEG
0.0 rpm
60.06 DROOP RATE
0.0%
60.07 MASTER SIGNAL 2
202
60.08 MASTER SIGNAL 3
213
70 DDCS CONTROL
70.01 CHANNEL 0 ADDR
1
70.02 CHANNEL 3 ADDR
1
70.03 CH1 BAUDRATE
2 Mbit/s
90 D SET REC ADDR
92 D SET TR ADDR
Visible only with a communication module active.
Refer to the Firmware Manual, Appendix B.
98 OPTION MODULES
Refer to the Firmware Manual, Appendix B.
⇒ Parameters to be set upon start-up.
*Visible only when Parameter 99.04 MOTOR
CTRL MODE is set to SCALAR.
**This parameter must be changed to
MASTER to activate communication to the
Follower(s).