Quick guide for selecting between gG and aR fuses

The table below is a short cut in selecting between gG and aR fuses. The
combinations (cable size, cable length, transformer size and fuse type) in the table
fulfil the minimum requirements for the proper operation of the fuse.
ACS800-01 size
Copper
Three-phase supply voltage 208 V, 220 V, 230 V or 240 V
-0025-2
3×25 Cu
-0030-2
3×35 Cu
-0040-2
3×50 Cu
-0050-2
3×70 Cu
-0060-2
3×95 Cu
-0070-2
3×120 Cu
Three-phase supply voltage 380 V, 400 V or 415 V
-0040-3
3×25 Cu
-0050-3
3×35 Cu
-0060-3
3×50 Cu
-0075-3
3×70 Cu
-0070-3 *
3×70 Cu
-0100-3
3×95 Cu
-0120-3
3×120 Cu
-0135-3
3×150 Cu
-0165-3
3×185 Cu
-0205-3
3×240 Cu
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V, 480 V or 500 V
-0050-5
3×25 Cu
-0060-5
3×25 Cu
-0070-5
3×35 Cu
-0105-5
3×70 Cu
-0100-5 *
3×70 Cu
-0120-5
3×95 Cu
-0140-5
3×95 Cu
-0165-5
3×150 Cu
-0205-5
3×185 Cu
-0255-5
3×240 Cu
1)
This cable type cannot be used in the drive because the lead-through in the drive is too small.
2)
This cable type cannot be used in the drive because the cable terminal is too small.
3)
This cable type cannot be used in the drive because the lead-through in the cable connection box is too small (see the
Dimensional
drawings).
4)
This cable type cannot be used in the drive because the cable lug is not designed for multiple wires.
* Type not available any more.
Technical data
Cable type
Aluminium
Max. cable length with gG fuses
10 m
3×35 Al
3×50 Al
3×70 Al
3×95 Al
3×120 Al
1)
3×185 Al
3×35 Al
3×50 Al
3×70 Al
100
2)
3×95 Al
130
3×95 Al
130
3×120 Al
150
1)
3×185 Al
170
3)
3×240 Al
200
3)
3×240 Al
240
4)
2×(3×95) Al
232
3×35 Al
3×50 Al
3×70 Al
130
2)
3×95 Al
160
3×95 Al
160
3×120 Al
190
3×150 Al
190
3)
3×240 Al
250
3)
3×240 Al
290
4)
2×(3×95) Al
289
Supply transformer minimum apparent power S
50 m
100 m
31
38
44
55
58
71
72
87
85
110
99
120
54
57
71
76
82
110
110
140
140
160
140
160
160
190
190
210
220
250
260
310
257
310
67
70
79
95
110
130
140
160
170
190
170
190
200
220
200
220
260
290
320
360
312
355
Max. cable length with aR fuses
10 m
100 m
-
27
27
-
33
33
-
41
41
-
55
70
-
65
70
-
81
81
48
48
58
58
70
70
99
99
96
96
120
120
140
140
160
160
180
180
134
153
56
56
68
68
83
83
130
130
110
120
140
140
160
160
200
200
230
230
167
185
(kVA)
N
200 m
-
-
-
-
-
-
48
58
70
140
140
140
140
160
200
196
56
68
83
150
150
150
160
200
230
218