Fuses

UL class T fuses for branch circuit protection are listed below. Fast acting class T or
faster fuses are recommended in the USA.
Check from the fuse time-current curve that the operating time of the fuse is
below 0.5 seconds for units of frame sizes R2 to R4 and 0.1 seconds for units
of frame sizes R5 and R6. The operating time depends on the supply network
impedance and the cross-sectional area and length of the supply cable. The short-
circuit current can be calculated as shown in section
page 110.
Note 1: See also
Note 2: In multicable installations, install only one fuse per phase (not one fuse per conductor).
Note 3: Larger fuses must not be used.
Note 4: Fuses from other manufacturers can be used if they meet the ratings and the melting curve of
the fuse does not exceed the melting curve of the fuse mentioned in the table.
ACS800-U1 type Frame size
Three-phase supply voltage 208 V, 220 V, 230 V or 240 V
-0002-2
R2
-0003-2
R2
-0004-2
R2
-0006-2
R3
-0009-2
R3
-0011-2
R3
-0016-2
R4
-0020-2
R4
-0025-2
R5
-0030-2
R5
-0040-2
R5
-0050-2
R6
-0060-2
R6
-0070-2
R6
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V or 480 V
-0004-5
R2
-0005-5
R2
-0006-5
R2
-0009-5
R2
-0011-5
R2
-0016-5
R3
-0020-5
R3
-0025-5
R3
-0030-5
R4
-0040-5
R4
-0050-5
R5
-0060-5
R5
-0070-5
R5
-0105-5
R5
-0100-5 *
R6
-0120-5
R6
-0140-5
R6
-0205-5
R6
Technical data
Planning the electrical
installation:
Input
current
A
A
5.2
10
6.5
10
9.2
15
18
25
24
30
31
40
38
50
49
70
64
90
75
100
102
125
126
175
153
200
190
250
4.1
10
5.4
10
6.9
10
9.8
15
13
20
18
25
24
35
31
40
40
50
52
70
63
80
77
100
94
125
138
150
121
150
155
200
179
225
243
350
Frame sizes R5 and R6
Thermal overload and short-circuit
Fuse
V
Manufacturer
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
600
Bussmann
on
protection.
Type
UL class
JJS-10
T
JJS-10
T
JJS-15
T
JJS-25
T
JJS-30
T
JJS-40
T
JJS-50
T
JJS-70
T
JJS-90
T
JJS-100
T
JJS-125
T
JJS-175
T
JJS-200
T
JJS-250
T
JJS-10
T
JJS-10
T
JJS-10
T
JJS-15
T
JJS-20
T
JJS-25
T
JJS-35
T
JJS-40
T
JJS-50
T
JJS-70
T
JJS-80
T
JJS-100
T
JJS-125
T
JJS-150
T
JJS-150
T
JJS-200
T
JJS-225
T
JJS-350