Cable types

The table below gives copper and aluminium cable types for different load currents.
Cable sizing is based on max. 9 cables laid on a cable ladder side by side, ambient
temperature 30 °C (86 °F), PVC insulation, surface temperature 70 °C (158 °F)
(EN 60204-1 and IEC 60364-5-52:2001). For other conditions, size the cables
according to local safety regulations, appropriate input voltage and the load current
of the drive.
concentric copper shield
Max. load
current
* This cable type cannot be used in this drive because the cable lug
is not designed for multiple wires.
Technical data
Copper cables with
Cable type
2
A
mm
13
3×1.5
18
3×2.5
24
3×4
30
3×6
42
3×10
56
3×16
71
3×25
88
3×35
107
3×50
137
3×70
167
3×95
193
3×120
223
3×150
255
3×185
301
3×240
Aluminium cables with
concentric copper shield
Max. load
Cable type
current
2
A
mm
61
3×25
69
3×35
83
3×50
107
3×70
130
3×95
151
3×120
174
3×150
199
3×185
235
3×240
274
3 × (3×50) *
260
2 × (3×95) *
3BFA 01051905