13.2 General Technical Data

Line power supply
Supply voltage
Supply voltage
Supply voltage
Supply voltage
AC line voltage low/line drop-out:
During low AC line voltage or a line drop-out, the drive continues until the intermediate circuit voltage drops below the
minimum stop level, which corresponds typically to 15% below the adjustable frequency drive's lowest rated supply voltage.
Power-up and full torque cannot be expected at AC line voltage lower than 10% below the adjustable frequency drive's lowest
rated supply voltage.
Supply frequency
Max. temporary imbalance between line phases
True Power Factor (λ)
Displacement Power Factor (cos ϕ)
Switching on input supply L1, L2, L3 (power-ups) ≤ 7.5 kW/10 HP
Switching on input supply L1, L2, L3 (power-ups) 11–75 kW/15–100 HP
Switching on input supply L1, L2, L3 (power-ups) ≥ 90 kW/125 HP
Environment according to EN60664-1
The unit is suitable for use on a circuit capable of delivering not more than 100kAIC RMS symmetrical Amperes, 240/480/600/
690 V maximum.
Motor output (U, V, W)
Output voltage
Output frequency (0.34–100 hp)/(125hp) [(0.25–75 kW) / (75 kW)]
Output frequency (125–1,350 hp)/(150 hp) [(90–1,000 kW)/(90 kW)]
Output frequency in flux mode
Switching on output
Ramp times
1)
Voltage and power dependent
Torque characteristics
Starting torque (Constant torque)
Starting torque
Overload torque (Constant torque)
3
13
Starting torque (Variable torque)
Overload torque (Variable torque)
Torque rise time in advanced vector control (independent of fsw)
Torque rise time in in flux vector control (for 5 kHz fsw)
1)
Percentage relates to the nominal torque.
2)
The torque response time depends on application and load but as a general rule, the torque step from 0 to reference is 4–5 x
torque rise time.
Digital inputs
Programmable digital inputs
Terminal number
Logic
Voltage level
Voltage level, logic'0' PNP
Voltage level, logic'1' PNP
Voltage level, logic '0' NPN
13-14
TM
AF-650 GP
2)
Design and Installation Guide
overvoltage category III/pollution degree 2
DET-767A
200–240 V ±
380–480 V ±10%
525–600 V ±10%
525–690 V ±10%
50/60 Hz ±5%
3.0% of rated supply voltage
≥ 0.9 nominal at rated load
near unity (> 0.98)
maximum 2 times/min.
maximum 1 time/min.
maximum 1 time/2 min.
0–100% of supply voltage
0–1,000 Hz
1)
0–800
Hz
0–300 Hz
Unlimited
0.01–3600 s.
1)
maximum 160% for 60 s
1)
maximum 180% up to 0.5 s
1)
maximum 160% for 60 s
1)
maximum 110% for 60 s
maximum 110% for 60 s
10 ms
1 ms
1)
4 (6)
1)
1)
18, 19, 27
, 29
, 32, 33,
PNP or NPN
0–24 V DC
< 5 V DC
> 10 V DC
> 19 V DC