RY10R2-TS contact output module
Item
Number of output points
Rated switching voltage/current
Minimum switching load
Maximum switching load
Response time
OFFON
ONOFF
Life
Mechanical
Electrical
Maximum switching frequency
Surge suppressor
Fuse
Withstand voltage
Isolation resistance
Noise immunity
Protection degree
Wiring method for common
Number of occupied I/O points
External interface
Internal current consumption (5VDC)
Weight
■Circuit configuration
Internal
circuit
3 SPECIFICATIONS
54
3.1 Performance Specifications
Specifications
16 points
24VDC 2A (resistive load)/point, 8A/common
240VAC 2A (COS = 1)/point, 8A/common
5VDC, 1mA
264VAC 125VDC
10ms or less
12ms or less
20 million times or more
Page 97 Relay life (contact switching life)
3600 times/hour
None
None
2300VACrms, 1 minute
10M or higher by isolation resistance tester
Simulator noise 1500Vp-p, noise width 1s,
noise frequency 25 to 60Hz (noise simulator condition)
IP1X
16 points/common (common terminal: 9)
16 points (I/O assignment: Output 16 points)
Two-piece spring clamp terminal block
Page 105 40-pin connector type module
450mA (TYP. all points ON)
0.19kg
Load
1
Load
17
9
100/200VAC
or 24VDC
Appearance