Mitsubishi Electric MELSEC iQ-R Series User Manual page 29

For melsec iq-r series programmable controllers
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

RX40C7 DC input module
Item
Number of input points
Rated input voltage
Rated input current
ON voltage/ON current
OFF voltage/OFF current
Input resistance
Response time
Withstand voltage
Isolation resistance
Noise immunity
Protection degree
Wiring method for common
Number of occupied I/O points
Interrupt function
External interface
Internal current consumption (5VDC)
Weight
■Circuit configuration
TB1
TB16
TB17
24VDC
24VDC
■Terminal connection
Connection diagram viewed from the front of the module
1
X01
2
3
X03
4
5
X05
6
7
X07
8
9
X09
10
11
X0B
12
13
X0D
14
15
X0F
16
17
18
X00 to X0F are signal names.
The number of 1 to 18 indicates a terminal number.
The terminal number 18 is empty.
Specifications
16 points
24VDC (ripple ratio: within 5%) (allowable voltage range: 20.4 to 28.8VDC)
7.0mA TYP. (at 24VDC)
15V or higher/4mA or higher
8V or lower/2mA or lower
3.3k
Page 28 Input response time
510VACrms, 1 minute
10M or higher by isolation resistance tester
Simulator noise 500Vp-p, noise width 1s,
noise frequency 25 to 60Hz (noise simulator condition)
IP2X
16 points/common (common terminal: TB17)
Positive/negative common shared type
16 points (I/O assignment: Input 16 points)
Available (can be set in the "Module Parameter")
18-point screw terminal block (M36 screw)
Page 104 18-point screw terminal block type module
110mA (TYP. all points ON)
0.16kg
Internal
circuit
X00
X02
X04
X06
X08
X0A
X0C
X0E
COM
24VDC
24VDC
Appearance
3 SPECIFICATIONS
3.1 Performance Specifications
3
27

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents