PDU8000 Modular Precision PDC
User Manual (FusionModule2000 V2.0)
Figure 5-6 Leveling the PDC
(1) Level
Step 10 Tighten the four M12 bolts.
In the cabinet combination scenario, the bolts need to be pretightened.
Step 11 (Optional) Combine cabinets.
1.
2.
3.
4.
5.
Issue 02 (2017-02-24)
Remove the front and rear doors of the PDC and level the PDC, as shown by (1) in
Figure
5-7.
Remove the cabinet connecting plates from the rack, as shown by (2) in
Secure the connecting plates in the connection positions on the front door using screws,
as shown by (3) in
Figure
Use the same method to secure the connecting plates in the connection positions on the
rear door.
A connecting plate is initially secured by one screw. Remove the screw from the column of the
adjacent cabinet to secure the connecting plate.
Ensure that both the vertical deviation and the distances between cabinets are within 3 mm after the
cabinets are combined.
Repeat the preceding steps to combine other PDCs.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
5-7.
5 Installation Guide
Figure
5-7.
39