Technical Specifications - Huawei PDU8000 User Manual

Modular precision pdc
Hide thumbs Also See for PDU8000:
Table of Contents

Advertisement

PDU8000 Modular Precision PDC
User Manual (FusionModule2000 V2.0)
Feature
Safe and reliable
Intelligent monitoring

3.4 Technical Specifications

Table 3-2 Technical Specifications
Item
Clear dimensions (mm)
Weight (kg)
Rated operating voltage (V)
Rated Insulation Voltage (V)
Rated frequency (Hz)
Rated operating current (A)
Enclosure protection level
Output circuit breakers
Surge protection level
Cabling
Certification compliance
Environmental friendliness
Issue 02 (2017-02-24)
Description
Certified by CCC and CE
Passed high/low temperature reliability tests
Reliable copper bar connection
Multi-functional isolation board that withstands fault arcs,
hot-swappable monitoring modules, and isolation of strong
current from weak current ensuring electrical reliability
Strong networking capabilities, alarm reporting, information
collection, and threshold setting
Intelligent measurement and monitoring
Real-time monitoring and alarm reporting
(Optional) Detecting the temperature features
Specifications
H x W x D: 2000 x 600 x 1100
About 350
208/220/380/400/415
690
50/60
400/250/160
IP20
Three-phase 16 A/20 A/32 A/40 A,or single-phase 10 A/16
A/32 A/40 A; max. 144 single-phase routes or 48
three-phase routes
Level C
Routed in and out from the top
CCC (GB 7251), CE (IEC 60950)
RoHS, REACH
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.