PDU8000 Modular Precision PDC
User Manual (FusionModule2000 V2.0)
Figure 5-32 Connecting the monitoring cable
(1) Monitoring cable outlet
Step 8 Use diagonal pliers to cut cable inlet and outlet holes on rodent-proof meshes based on the
number and specifications of cables to be routed.
Figure 5-33 Cutting holes in the rodent-proof meshes
Step 9 Reinstall the rodent-proof meshes.
Step 10 Seal cable inlet and outlet holes on the PDC using firestop putty.
Step 11 Reinstall the transparent covers of the input copper bar and N bar.
When installing the transparent cover for the N bar, verify that one side of the cover is flush with the
outer side of the N bar.
----End