EN – Main switch and EMC C1 filter options installation supplement 13
Compliance with the EN 61800-3:2004 + A1:2012 with
options with EMC C1 filter (+E223 and +F316)
Note: To be able to use EMC C1 filter (+E223 or +F316), you must set parameters
97.01 Switching frequency reference and 97.02 Minimum switching frequency to the
value of 2 kHz.
Conducted emissions
• C1 compliance when using maximum 10 m motor cable
• C2 compliance when using maximum 100 m motor cable
• C3 compliance when using maximum 150 m motor cable.
Radiated emissions
• C1 compliance not applicable.
• C2 compliance when using minimum 5 m motor cable.
• C3 compliance when using minimum 5 m motor cable.
The conducted and radiated emission limits are complied with the following
provisions:
1. The EMC C1 filter is installed as specified in this supplement.
2. The motor and control cables are selected as specified in the Hardware manual of
the drive.
3. The drive is installed according to the instructions given in the Quick installation
and start-up guide for frames R1 to R5 of the drive and this supplement.
WARNING! In a domestic environment, this product may cause radio inference, in
which case supplementary mitigation measures may be required.
WARNING! The drive may cause radio interference if used in residential or domestic
environment. The user is required to take measures to prevent interference, in
association to the requirements for the CE compliance listed above, if necessary.
Notes:
• A drive with the internal EMC filter connected can be installed to a symmetrically
grounded TN-S system. If you install the drive to another system, check if you
must disconnect the EMC filter. See section Checking the compatibility with IT
(ungrounded), corner-grounded delta, midpoint-grounded delta, and TT systems
in chapter Electrical installation – IEC or Electrical installation – North America in
the Hardware manual of the drive.
WARNING! Do not install a drive with the EMC filter connected to a system
that the filter is not suitable for. This can cause danger, or damage the drive.