1ZSC000562-AAL en Vacuum on-load tap-changers, type VUBB User’s guide...
Page 2
Any specific application not covered should be referred directly to ABB or its authorized representative. ABB makes no warranty or representation and assumes no liability for the accuracy of the information in this document or for the use of such information. All information in this document is subject to change without notice.
Content 1. Safety ..........................5 1.1 General ........................5 1.2 Safety warnings ......................5 1.3 Safety precautions ....................5 1.3.1 Personal safety ....................5 1.3.2 Environmental safety ................... 5 1.3.3 First aid ......................5 1.3.4 In the event of fire ....................5 2.
Page 4
4. Operation ......................... 29 4.1 Synchronization between tap-changer and motor-drive mechanism ......29 5. Inspection ......................... 30 5.1 General ........................30 5.2 Inspection ......................... 30 5.3 Checking oil quality ....................31 5.4 Maintenance ......................31 5.5 Replacement of the complete switching mechanism including vacuum interrupters .. 31 6.
Avoid vomiting. 1. Drink water or milk. 2. Call a doctor. 1.3.4 In the event of fire In the event of fire, extinguish with a powder, foam or carbon acid extinguishing agent. 1ZSC000562-AAL en | User’s guide VUBB 5...
(dehydrating breather or one-way breather). Make sure that no The electrical circuit principle for the VUBB is shown in open fires, hot surfaces or sparks are present in the Figs. 1-18. The purpose of the operation is to commute the immediate surroundings of the breathing devices.
Page 8
Fig. 7. 8. Main auxiliary contact connects to fixed contact 2. Fig. 8. 9. Main vacuum interrupter closes, commuting the load current to the main branch. Continuous load on fixed contact 2. Fig. 9. 8 User’s guide VUBB | 1ZSC000562-AAL en...
3. Main auxiliary contact disconnects from fixed contact 2. Fig. 12. 4. Main auxiliary contact connects to fixed contact 1. Fig. 13. 5. Main vacuum interrupter closes. The load current commutes to the main branch, producing a circulating current. Fig. 14. 1ZSC000562-AAL en | User’s guide VUBB 9...
The VUBB tap-changer is of the in-tank design. The motor- drive mechanism is attached to the transformer tank and connected to the tap-changer by means of drive shafts and a bevel gear.
Coarse/fine switching (type D) With coarse/fine switching, the change-over selector extends the regulating range to twice the voltage of the tapped winding by connecting or disconnecting the coarse regulating winding. Fig. 23. Coarse/fine switching. 12 User’s guide VUBB | 1ZSC000562-AAL en...
Fig. 24. Three-phase, star point connection. Three-phase delta, fully insulated (T) Only one unit is required for all three phases. Fig. 25. Three-phase delta, fully insulated connection. 1ZSC000562-AAL en | User’s guide VUBB 13...
Sections 2.2.1 and 2.2.2. the tap-changer. Energy is provided from a motor through a series of gears and out through a drive shaft. Several features The VUBB tap-changer contains three selector switches, one are incorporated within the mechanism to lengthen service per phase.
The unit’s serial number is on the top flange of the tap- changer. Oil test according to IEC 60422 2005. Fig. 27. Example of rating plate. Fig. 28. Location of serial number plate and rating plate. 16 User’s guide VUBB | 1ZSC000562-AAL en...
The following greases (ball bearing greases) or similar are Remember to place O-rings on the flanges. required during installation: – GULF-718 EP – Mobil-Grease 28 – SHELL-Aero Shell Grease 22 1ZSC000562-AAL en | User’s guide VUBB 17...
O-rings on the flanges. CAUTION Wait at least three hours before energizing the transformer after filling oil at atmospheric pressure. This waiting period is necessary to allow air bubbles to dissipate. 18 User’s guide VUBB | 1ZSC000562-AAL en...
Transformer Tap-changer tap-changer. 8. Connect the breathing device to the oil conservator for the Fig. 29. Vacuum filling overview. tap-changer. Make sure the connection to the breathing device is properly sealed. 1ZSC000562-AAL en | User’s guide VUBB 19...
The tubes around shafts and couplings are for protection. 20 User’s guide VUBB | 1ZSC000562-AAL en...
Page 21
7. Position the two protective tubes with the slotted ends Fig. 38. The couplings should be offset 90° in relation to each other. outwards. See Fig. 36. Fig. 36. Position the tubes with the slotted ends outwards. 1ZSC000562-AAL en | User’s guide VUBB 21...
Page 22
16. Push the two protective tubes horizontally until they touch the bevel gears. See Fig. 40. Fig. 42. Self-adhesive information plates on the tubes. Fig. 40. Push the two protective tubes horizontally. 22 User’s guide VUBB | 1ZSC000562-AAL en...
4. Fit six screws and washers in the holes on the coupling halves. See Fig. 44. Fig. 46. Tighten the remaining screws. Fig. 44. Fit screws and washers to the coupling halves. 1ZSC000562-AAL en | User’s guide VUBB 23...
Page 24
See Fig. 51. Fig. 48. Place protective tubes on the vertical drive shaft. Multi-hole coupling flanges 9. Fit two hose clips. See Fig. 49. Fig. 51. BUE multi-hole coupling. Fig. 49. Fit two hose clips. 24 User’s guide VUBB | 1ZSC000562-AAL en...
Page 25
20. Secure the tube with a hose clip. See Fig. 56. 15. Fit six screws and washers in the holes on the coupling halves (see Fig. 44) and tighten them lightly. Fig. 56. Fit a hose clip. 1ZSC000562-AAL en | User’s guide VUBB 25...
Page 26
See Fig. 60. 22. If the motor-drive mechanism is out of position, manually crank the motor-drive mechanism to the exact position Fig. 60. Position indicator on the tap-changer. according to the info box above. 26 User’s guide VUBB | 1ZSC000562-AAL en...
21. Operate the tap-changer electrically to the other end- For a BUL2 motor-drive mechanism, continue at step 7. position. 22. Repeat the test procedure above. For a BUE motor-drive mechanism, continue at step 10. 1ZSC000562-AAL en | User’s guide VUBB 27...
BUE and BUL installation and commissioning guide. Check the oil level one month after filling. It is usual for the oil level of the oil conservator to decrease due to gas absorption in the oil. 28 User’s guide VUBB | 1ZSC000562-AAL en...
Fig. 63. Clearance at the bottom of the tube. 6. Secure the tube with the hose clip. See Fig. 64. Fig. 61. Turning the shaft between end-positions. Fig. 64. Secure the hose clip. 1ZSC000562-AAL en | User’s guide VUBB 29...
5. Inspection The VUBB tap-changer has been designed to provide 5.2 Inspection maximum reliability. The simple and robust design provides It is recommended that the tap-changer be inspected at the a service life equal to the service life of the transformer.
ABB. An oil filter unit is normally not required on the VUBB tap- changer. But, if the tap-changer is equipped with an oil filter The estimated contact life of the vacuum interrupters in the unit from ABB, it should be inspected once a year.
There is a leakage in the connections to the conservator. Drying agent has changed color from the top of the breather Locate the leakage and seal it. CAUTION Do perform service on the transformer after a pressure relay trip; contact the manufacturer. 32 User’s guide VUBB | 1ZSC000562-AAL en...
7. Repairs and adjustments 7.1 General 7.2.2 Tools required Repairs on the VUBB tap-changer fall into two categories: Standard set of metric combination wrenches. Repairs – Replacing worn or end-of-service-life parts 7.2.3 Materials and spare parts required – O-rings Modifications – Improving the already very high standard of –...
Page 34
10 cm procedure: If the leakage is in the gear box (from the tap- changer into the gear box), contact ABB for further instructions. Fig. 67. Procedure for lifting the cover. 11. Be sure that the oil level in the tap-changer is lowered by 100-150 mm.
Synchronize the shaft as described in section 4.1. the function test, it must be replaced. This is described in the assortment guide. CAUTION It is not permitted to only replace the microswitch inside the pressure relay. 1ZSC000562-AAL en | User’s guide VUBB 35...
On the following pages, the standard circuit diagrams and the contact timing diagrams for BUE and BUL2 are shown. Be sure to use the circuit diagram and the contact timing diagram delivered with your tap-changer. 36 User’s guide VUBB | 1ZSC000562-AAL en...
ITEM Q1 OFF/RUN- STEP-BY-STEP STEP-BY-STEP REMOTE LOCAL UPPER LIMIT LOWER LIMIT THROUGH ALARM IN OPERATION DE-ENERGIZED CONTACTS OPEN TOWARDS ITEM F2 OFF TAP-CHANGE IN ITEM Q1 ON ITEM Q1 OFF TAP-CHANGE REMOTE LOCAL PROGRESS INCOMPLETE 1ZSC000562-AAL en | User’s guide VUBB 39...
Power supply unit, 100-240 V AC /24 V DC Terminal board group Internal terminal board group TAP-CHANGE OPERATION n → n+1 1 tap LOCAL control n → n-1 1 tap REMOTE control Upper limit-position Protective ground Lower limit-position Crank 40 User’s guide VUBB | 1ZSC000562-AAL en...
9.3.3 Selector switch Material Approximate amount (kg) 9.2 Weights Aluminum The approximate weight of the VUBB tap-changer is specified Copper below. The specified weights do not include the weights of Fiberglass 49.6 the motor-drive mechanism and the drive shaft system.