8 COMMUNICATIONS
Table 8–6: 745 MEMORY MAP (Sheet 21 of 57)
GROUP
ADDR
DESCRIPTION
(HEX)
TRANSFORMER
1102
Transformer Type
continued
1103
Rated Winding Temperature Rise
1104
Type of Cooling: Oil Immersed
1105
Load Loss at Rated Load (2 registers)
1107
No-Load Loss
1108
Top Oil Rise Over Ambient (at rated load)
1109
Transformer Thermal Capacity
110A
Winding Time Constant: Oil-Immersed
110B
Type of Cooling: Dry
110C
Thermal Time Constant: Dry
110D
Set Initial Accumulated Loss of Life
110E
Frequency Tracking
110F
Reserved
111F
Reserved
WINDING 1
1120
Winding 1 Nominal Phase-to-Phase Voltage
1121
Winding 1 Rated Load
1122
Winding 1 Phase CT Primary
1123
Winding 1 Ground CT Primary
1124
Winding 1 Series 3-Phase Resistance
1125
Reserved
112F
Reserved
WINDING 2
1130
Winding 2 Nominal Phase-to-Phase Voltage
1131
Winding 2 Rated Load
1132
Winding 2 Phase CT Primary
1133
Winding 2 Ground CT Primary
1134
Winding 2 Series 3-Phase Resistance
1135
Reserved
113F
Reserved
WINDING 3
1140
Winding 3 Nominal Phase-to-Phase Voltage
1141
Winding 3 Rated Load
1142
Winding 3 Phase CT Primary
1143
Winding 3 Ground CT Primary
1144
Winding 3 Series 3-Phase Resistance
1145
Reserved
GE Power Management
RANGE
1 to 20000
0.1 to 2000
1 to 200
0.00 to 200.00
0.25 to 15.00
0.25 to 15.00
0 to 20000
1 to 20000
1 to 20000
1 to 50000
1 to 50000
0.001 to 50.000
1 to 20000
1 to 20000
1 to 50000
1 to 50000
0.001 to 50.000
1 to 20000
1 to 20000
1 to 50000
1 to 50000
0.001 to 50.000
745 Transformer Management Relay
8.3 MODBUS MEMORY MAP
STEP
UNITS
FORMAT
VALUE
---
---
---
---
---
---
---
---
---
1
kW
0.1
kW
1
°C
0.01
kWh/°C
0.01
minutes
-
-
-
0.01
minutes
1
hrs x 10
---
---
---
---
kV
---
MVA
1
:1 or :5 A
1
:1 or :5 A
0.001
---
kV
---
MVA
1
:1 or :5 A
1
:1 or :5 A
0.001
---
kV
---
MVA
1
:1 or :5 A
1
:1 or :5 A
0.001
FACTORY
CODE
DEFAULT
F28
3 = Y/d30°
F37
1 = 65°C (oil)
F39
0 = 0A
F101
1250 kW
F90
1250=125.0 kW
F1
10°C
F3
100=1.00 kWh/°C
F3
200 = 2.00 min
F100
0=sealed self-cooled
F3
200 = 2.00 min
F1
0 hours
F30
1 = Enabled
F90
220.0 kV
F90
1000 = 100 MVA
F1
500 A
F1
500 A
10700 = 10.7 Ω
F53
F90
690 = 69.0 kV
F90
1000 = 100 MVA
F1
1500 A
F1
1500 A
2100 = 2.100 Ω
F53
8
F90
690 = 69.0 kV
F90
1000 = 100 MVA
F1
1500 A
F1
1500 A
2100 = 2.100 Ω
F53
8-37