Select The Power Cables; Ensure The Cooling; Protect The Drive And Input Power Cable; Install The Drive On The Wall - ABB ACQ580-01 Quick Installation And Start-Up Manual

Drives for water, frames r1 to r
Table of Contents

Advertisement

16 EN – R1...R4 Quick installation guide

Select the power cables

Size the power cables according to local regulations to carry the nominal current
given on the type designation label of your drive.

Ensure the cooling

R1-
R4
See table
IEC ratings at UN = 230 V, 400 V and 480 V
R5
dissipation. The allowed operating temperature range of the drive is -15 to +50 °C (+5
to +122 °F). No condensation or frost is allowed. For more information on the ambient
R6-
temperature and derating, see chapter Technical data in ACQ580-01 (0.75 to 250
R9
kW) hardware manual (3AXD50000044862 [English]).

Protect the drive and input power cable

EN
See tables
gG fuses
If you use gG fuses, make sure that the operating time of the fuse is below
DE
0.5 seconds. Follow the local regulations.
ES

Install the drive on the wall

FI
See figure
R1...R4 Figures A
FR

Check the insulation of the power cables and the motor

RU
Check the insulation of the input cable according to local regulations before
connecting it to the drive.
SV
See figure
B1
on page 51.
1. Check the insulation of the motor cable and motor when the cable is disconnected
from the drive. Measure the insulation resistance between each phase conductor
and then between each phase conductor and the Protective Earth conductor
using a measuring voltage of 1000 V DC. The insulation resistance of a typical
motor must exceed 100 Mohm (reference value at 25 °C or 77 °F). For the
insulation resistance of motors, see the manufacturer's instructions.
Note: Moisture inside the motor casing will reduce the insulation resistance. If
moisture is suspected, dry the motor and repeat the measurement.
(on page 11) and
uR or aR fuses
on page 51.
on page
9
for the heat
(on page 12).