Detailed Description Of The Objects - ABB i-bus EIB Product Manual

Dim actuator modules for the room controller, intelligent installation systems
Hide thumbs Also See for i-bus EIB:
Table of Contents

Advertisement

®
ABB i-bus
EIB / KNX
4.11 Communication objects
4.11.1 Overview
© 2004 ABB STOTZ-KONTAKT GmbH
Project design and programming
General objects
No
Function
0/15
Switch
Switches the output on or off.
1/16
Status switch
Used to report the current switching state. It can be inverted if required.
2/17
Relative dimming
Dimming commands (BRIGHTER, DARKER, STOP) are received via this object.
3/18
Brightness value
Assigns a brightness value to the output. It is possible to dim or jump to the brightness value.
4/19
Status brightness value
Used to report the current brightness value that has been issued. The object value updates
itself in connection with a switching or dimming process.
5/20
Priority / forced operation
This object is used to preassign a parameterisable brightness value with subsequent blocking
of the operation.
6
Error report
(only Universal Dim Actuator Module UD/M 1.300.1)
This object reports a general error.
7
Error code
(only Universal Dim Actuator Module UD/M 1.300.1)
Gives detailed information about the cause of an error which has occurred. The object value
is sent in the event of a change.
18
Light sensor value
(only Light Controller Module LR/M 1.6.1)
This object sends the brightness value which has been measured by the light sensor.
Objects for the "Preset" function
No
Function
8/23
Call preset 1/2 and
10/25
Call preset 3/4
Retrieves a parameterisable brightness value.
"0" retrieves preset1 or preset3
"1" retrieves preset2 or preset4
9/24
Set preset 1/2 and
11/26
Set preset 3/4
Stores the current brightness value as a new preset value.
"0" stores preset1 or preset3
"1" stores preset2 or preset4
Objects for the "Lighting control" function
No
Function
12
Set setpoint value
If the device receives the value "1" via this object, the current light sensor value (actual value)
is adopted as the new setpoint value of the control function.
Object name
Data type
Output A
1 Bit (EIS1)
Output A
1 Bit (EIS1)
Output A
4 Bit (EIS2)
Output A
1 Byte (EIS6)
Output A
1 Byte (EIS6)
Output A
2 Bit (EIS8)
Output A
1 Bit (EIS1)
1 Byte (EIS14)
Output A
Input light sensor
1 Byte (EIS6)
Object name
Data type
Output A
1 Bit (EIS1)
Output A
1 Bit (EIS1)
Object name
Data type
Light control
1 Bit (EIS1)
Flags
CW
CRT
CW
CW
CRT
CW
CRT
CRT
CRT
Flags
CW
CW
Flags
CW
38

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents